Wiring

Please note:

}

Information given in the "Technical details" must be followed.

}

Outputs 13-14, 23-24, 33-34, 43-44, 63-64, 73-74, 83-84, 93-94 are safety contacts;

output 51-52 is an auxiliary contact (e.g. for display).

}

Auxiliary contact 51-52 should

not be used for safety circuits!

}

To prevent contact welding, a fuse should be connected before the output contacts (see

technical details).

}

Calculation of the max. cable length l

max

in the input circuit:

R

lmax

R

l

/ km

I

max

=

R

lmax

= max. overall cable resistance (see technical details)

R

l

/ km = cable resistance/km

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in-

ductive loads.

Preparing for operation

}

Supply voltage

Supply voltage

AC

DC

A1
A2

24 V DC

0 V

PNOZsigma

expansion

module

}

Input circuit

Input circuit

Single-channel

Dual-channel

Base unit:

Safety relay PNOZ X

A1
A2

24 V DC

0 V

PNOZsigma

expansion

module

Base unit:

PNOZelog safety relay

Driven via semiconductor

outputs (24 VDC)

A1

A2

0 V

O1

L-

PNOZsigma

expansion

module

This manual is related to the following products: