In1, In2 alternately

Fault

Diagnostics: Connection error or short between S12 and S22 detected or inter-

nal error

}

Remedy: Rectify connection error or short across contacts, switch supply

voltage off and then on again.

In1

Fault

Diagnostics: Simultaneity exceeded: Channel 1 too late or power-up blocked

due to short-term interruption at S11; input circuits not operated simultaneously

}

Remedy: Open both input circuits, S12 and S22, simultaneously and then

close again.

In2

Fault

Diagnostics: Simultaneity exceeded: Channel 2 too late or power-up blocked

due to short-term interruption at S21; input circuits not operated simultaneously

}

Remedy: Open both input circuits, S12 and S22, simultaneously and then

close again.

Faults - malfunctions

}

Contact malfunctions: If the contacts have welded, reactivation will not be possible after

the input circuit has opened.