beautypg.com

Pilz PNOZ s6 C 48-240VACDC 3 n/o 1 n/c User Manual

Page 13

background image

PNOZ s6

Operating Manual PNOZ s6
21398-EN-08

13

Relay outputs

750106

750136

751106

751136

Contact fuse protec-

tion, external safety

contacts

In accordance

with the standard

EN 60947-5-1

EN 60947-5-1

EN 60947-5-1

EN 60947-5-1

Blow-out fuse,

quick

10 A

6 A

10 A

6 A

Blow-out fuse,

slow

6 A

4 A

6 A

4 A

Circuit breaker,

24V AC/DC, char-

acteristic B/C

6 A

4 A

6 A

4 A

Contact fuse protec-

tion, external auxilia-

ry contacts

Blow-out fuse,

quick

10 A

6 A

10 A

6 A

Blow-out fuse,

slow

6 A

4 A

6 A

4 A

Circuit breaker,

24 V AC/DC,

characteristic B/C

6 A

4 A

6 A

4 A

Contact material

AgCuNi + 0,2 µm

Au

AgCuNi + 0,2 µm

Au

AgCuNi + 0,2 µm

Au

AgCuNi + 0,2 µm

Au

Conventional ther-

mal current while

loading several

contacts

750106

750136

751106

751136

Ith per contact at UB

AC

Conv. therm. cur-

rent with 1 con-

tact

6,00 A

6,00 A

Conv. therm. cur-

rent with 2 con-

tacts

6,00 A

6,00 A

Conv. therm. cur-

rent with 3 con-

tacts

4,50 A

4,50 A

Ith per contact at UB

DC

Conv. therm. cur-

rent with 1 con-

tact

6,00 A

6,00 A

6,00 A

6,00 A

Conv. therm. cur-

rent with 2 con-

tacts

6,00 A

6,00 A

6,00 A

6,00 A

Conv. therm. cur-

rent with 3 con-

tacts

6,00 A

4,50 A

6,00 A

4,50 A