Status indicators, Error indicators – Pilz PNOZ s6 C 48-240VACDC 3 n/o 1 n/c User Manual

Page 7

background image

PNOZ s6

Operating Manual PNOZ s6
21398-EN-08

7

Information
Status indicators and error indicators may occur independently. In the case
of an error display, the "Fault" LED will light or flash (exception: "Supply
voltage too low"). An LED that is also flashing indicates the potential cause
of the error. An LED that is lit and is static indicates a normal operating sta-
tus. Several status indicators and error indicators may occur simultaneously.

Status indicators

Power

Supply voltage is present.

In1

Pushbutton at S11 is operated.

In2

Pushbutton at S21 is operated.

Out

Safety contacts are closed and semiconductor output Y32 carries a high signal.

Reset

24 V DC is present at S34.

Error indicators

All LEDs off

Diagnostics: Short across contacts/earth fault; unit switched off

}

Remedy: Rectify short across contacts/earth fault, switch off supply voltage

for 1 min.

Fault

Diagnostics: Plug terminator not connected

}

Remedy: Insert plug terminator, switch supply voltage off and then on

again.

Fault

Diagnostics: Internal error, unit defective

}

Remedy: Switch supply voltage off and then on again, change unit if neces-

sary.

Power

Diagnostics: Supply voltage too low

}

Remedy: Check the supply voltage.