Status indicators, Error indicators – Pilz PNOZ s6 C 48-240VACDC 3 n/o 1 n/c User Manual
Page 7

PNOZ s6
Operating Manual PNOZ s6
21398-EN-08
7
Information
Status indicators and error indicators may occur independently. In the case
of an error display, the "Fault" LED will light or flash (exception: "Supply
voltage too low"). An LED that is also flashing indicates the potential cause
of the error. An LED that is lit and is static indicates a normal operating sta-
tus. Several status indicators and error indicators may occur simultaneously.
Status indicators
Power
Supply voltage is present.
In1
Pushbutton at S11 is operated.
In2
Pushbutton at S21 is operated.
Out
Safety contacts are closed and semiconductor output Y32 carries a high signal.
Reset
24 V DC is present at S34.
Error indicators
All LEDs off
Diagnostics: Short across contacts/earth fault; unit switched off
}
Remedy: Rectify short across contacts/earth fault, switch off supply voltage
for 1 min.
Fault
Diagnostics: Plug terminator not connected
}
Remedy: Insert plug terminator, switch supply voltage off and then on
again.
Fault
Diagnostics: Internal error, unit defective
}
Remedy: Switch supply voltage off and then on again, change unit if neces-
sary.
Power
Diagnostics: Supply voltage too low
}
Remedy: Check the supply voltage.