beautypg.com

Wiring, Pin assignment, connector and cable, Connection to evaluation devices – Pilz PSEN cs4.1a User Manual

Page 8

background image

PSEN cs4.1a/b/p/M12

Operating Manual PSEN cs4.1a/b/p/M12
22187-EN-02

8

Wiring

Please note:

}

Information given in the "Technical details" must be followed.

}

Calculation of the max. cable length l

max

in the input circuit:

R

lmax

R

l

/ km

I

max

=

R

lmax

= Max. overall cable resistance (see

Technical details [

20]

R

l

/ km = cable resistance/km

Pin assignment, connector and cable

1

2

3

4

8

5

6

7

Fig.: 8 pin M8/M12 connector

PIN

Pin

designation

Function

Wire colour

1

S21

Input, channel 2

White

2

A1

+24 VUB

Brown

3

12

Output, channel 1

Green

4

22

Output, channel 2

Yellow

5

Y32

Signal output

Grey

6

S11

Input, channel 1

Pink

7

A2

0 V UB

Blue

8

-

Do not connect

Red

The wire colour also applies for the cable available from Pilz as an accessory.

Connection to evaluation devices
Please note:

}

The power supply must meet the regulations for extra low voltages with safe separation

(SELV, PELV).

}

The inputs and outputs of the safety switch must have a safe separation to voltages

over 60 V AC.

CAUTION!
The safety outputs must use 2-channel processing.

This manual is related to the following products: