59

Unit operates but the power switch light is not ON

Possible Cause

Solution

Bulb is burned out

Replace bulb

Unit is leaking water

Possible Cause

Solution

Piping from unit to drain is trapped

Trap plugged

Condensate pan plugged

Unit not level

Re-pipe to remove external traps

Clean trap

Remove blockage and clean

Level with shims

Unit is running properly, but the sound of the unit objectionable

Possible Cause

Solution

Noise is from airflow

Noise is from unit

Redirect airflow
Add baffles
Add insulated ductwork

Add sound baffle between unit and occupied

High Pressure Switch has Shut the Unit Down

Every Wine Guardian unit has a manual reset high pressure switch in the refrigeration system.
This switch shuts the compressor and condenser down if the head pressure in the system is too
high. It is intended to protect the compressor. Restricted airflow through the condenser is the most
common reason for the pressure becoming too high. This can be caused by dust covering the filter
or an obstruction blocking the airflow in the duct or grille.

Possible Cause Solution

Head pressure in unit is too high because

Remove the obstruction at the condensing unit or

an obstruction is restricting air flow clean the condenser coil. Then restart the unit
after resetting the using the high pressure switch.