48

Differential
temperature
adjustment



Setting 16

Press “Mode” button to advance to Setting 16.

Press the “Up” or “Down” buttons to adjust to
the desired set point.


This setting changes the system/compressor and
turns on temperature above setpoint. Factory
default is set to +1
Example: Sensor reading = 55 Deg F
Setting 16 Set to +3
System/compressor turns on at 58 Deg F

Deadband setting



Setting 17

Press “Mode” button to advance to Setting 17.

Press the “Up” or “Down” buttons to adjust to
the desired setpoint.

This setting is the minimal allowable temperature
difference between heating and cooling setpoints.
Maximum is 5 Deg, minimum is 1 Deg. Factory
default is set to 2 Degrees.



Test mode setting

Setting 18

Press “Mode” button to advance to Setting 7.

Press the “Up” or “Down” buttons to adjust to
the desired setpoint. When set to one (1) the
controller will automatically turn on all
outputs with the exception of electric heat.
Factory default is zero (0).

Zero (0) = Off

One (1) = On

System Selection











Setting 19

DO NOT CHANGE