quarter inch, a vibration eliminator should be installed close to the motor compressor in a
horizontal parallel to the compressor, crankshaft or in a vertical position 90 degrees to
compressor crankshaft.

NOTE: The suction line should be clamped near the inlet end of the vibration
eliminator. The vibration eliminator is located between the clamp and the
compressor

.


Split System Interconnecting Line Sizing Chart

Table 3

Model

Liquid
Line(OD)

Liquid
connection
at
evaporator
(OD)

Suction
line (OD)

Min.
Suction line
insulation
thickness
(in)

Suction
connection
at
evaporator
(OD)

Maximum
“total” line
length

Maximum
lift
(height)

SS025

1/4”

1/4”

3/8”

3/8”

3/8”

50’

15’

SS050

1/4”

1/4”

1/2”

3/8”

*3/8”

50’

15’

SS088

3/8”

*1/4”

1/2”

5/8”

1/2”

50’

15’

SS200

3/8”

3/8”

7/8”

5/8”

*1/2”

50’

15’

*Interconnecting tube must be reduced down at evaporator connection

Notes:

Line lengths are expressed in equivalent feet = actual run length + fitting allowances (i.e.
~5’ for each bend/elbow allowance).

Use only refrigeration grade dehydrated tubing.

Install refrigeration piping per local codes and ASHRAE guidelines.