background image

47

Advanced Settings--
Special access
required. Contact
Wine Guardian
Service Department
for access code

Setting 8

Press “Mode” button to advance to Setting 8.

Press the up or down arrow buttons to adjust

number to the access code. Press “Mode”
button to continue onto setting 9 through 19.


Compressor anti-
short cycling time

Setting 9

WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER THAN
FACTORY DEFAULT
.

Press “Mode” button to advance to Setting 9.

Press the “Up” or “Down” arrow buttons to
adjust to the desired time in one (1) minute
increments. Maximum is 10 minutes,
minimum is 0 minutes.

Compressor anti-short cycling time is the
amount of allowable time between compressor
stop and restart. Rapid start/stop of compressors
can cause premature failure. Factory default is 5
minutes.

Set up remote sensor
or remote interface
controller

Setting 10

Press “Mode” button to advance to Setting 10.

Press the “Up” or “Down” arrow buttons to
adjust to the desired setting.

rS = Remote sensor
rI = Remote interface
LI= Local interface – Through-the-wall unit

only
A = Averaging – Jumper position within

sensors must be adjusted. See page 44.










Room sensor
calibration

Setting 15

Press “Mode” button to advance to Setting 15.

Press the “Up” or “Down” buttons to adjust to
the desired set point. Maximum setting is +5,
minimum setting is -5. Factory default is zero
(0). Sensor calibration set point changes the
actual display reading (temperature only) by
the value of this setting.

Example: Sensor reading = 55 Deg F
Setting 15 set to +4
Display reading = 59 Deg F