Unit is operating and blows evaporator air,

but the supply air is not colder than the return air from the cellar

Possible Cause Solution

Remote interface controller not set up Check remote interface controller setup in the
properly manufactures guide

Compressor not operating High pressure switch open (button up)
Alarm will appear on remote interface controller

Condenser airflow is blocked Remove blockage

Clean filter and coil (if needed)

Head Pressure (HP) switch is open
Reset HP switch See reset instructions on pg. 60

Cellar temperature too cold (below 51 degrees) when unit is running

Possible Cause

Solution

Remote interface controller set too low on
cooling

Heating coil (optional) not operating

Remote interface controller set too low on
heating

Remote interface controller not controlling
temperature

Reset remote interface controller to higher
cooling temperature

Check for remote interface controller rise across
coil

Reset remote interface controller to higher
heating temperature

Remote interface controller mounted in improper
location

Cellar temperature too cold (below 51 degrees) when unit is not running

Possible Cause

Solution

Too much heat loss to adjacent spaces

Cellar loads are too high

Increase insulation around the ductwork
Check and clean filter and coil
Coil frozen – shut off unit for two hours

Install additional insulation

Humidity too low or supply air is too cold, without optional humidifier

Possible Cause

Solution

Not enough evaporator airflow

Defective thermal expansion valve

Temperature set too cold

Remove blockage in supply or return ductwork
Check and clean filter and coil
Coil frozen – shut off unit for two hours

If under warranty call for service
If not under warranty call a refrigeration
technician

Raise temperature setpoint