SYSTEM OPERATION

Initial Start-Up

When power is applied to the unit, the control will briefly

display all symbols, and the Snowflake symbol will be displayed

(if unit is calling for cooling). There may be a brief (up to 60

sec.) delay prior to the evaporator fan turning on. When the

evaporator fan is activated the Fan symbol will display.

APST (Advance Product Safety Technology) is a temperature

control feature for the evaporator fan that comes standard with

all WhisperKOOL units. APST ensures that in the possible event

of a cooling deficiency, the heat from the indoor fan will not

raise the temperature of the wine cellar, which could otherwise

have an adverse effect on the wine-aging process.

Set Point

The set point is set from the factory (WhisperKool) at 55F°. It

can be adjusted by the customer between 45–67F° in one

degree increments.

Humidity Features

The FON function is an adjustable feature which allows the

customer the convenience of reintroducing some of the

humidity removed by the fan coil during the cooling process.

The FON Function controls the evaporator fan operation

once the set point has been reached. When the bottle probe

has reached the set point (all units are shipped with the set

point of 55°F and a differential of 1°), the compressor and the

condenser fan will turn off, but the indoor fan will continue

to run for about 5 minutes to re-introduce any moisture from

the evaporator coil. All units come with this feature turned

off. If low humidity is a problem an increase in this setting

will raise the humidity level. The FON function is one of the

many Customer Preference Selection features that allow the

customer the ability to fine-tune the controls.

The Fon parameter can be increased to allow the evaporator

and condenser fans to run for a longer period of time after

the compressor turns off, allowing more moisture to be re-

introduced into the wine cellar.

Anti-Short Cycle

The Anti-Short Cycle ensures that the unit will remain off for a

period of five minutes after the unit has reached the set point

to allow the pressure in the refrigeration system to equalize

prior to starting the compressor.

Anti-Frost Cycle (defrost)

The system will go through an Anti-Frost cycle every 4 hours.

This will shut down the compressor and allow the evaporator

and condenser fans to run to evaporate any frost accumulation

on the coil. The compressor will remain off until the evaporator

coil reaches 40F°, or for a maximum of ten minutes. The unit

will then return to normal operation.

Low Ambient Conditions

If the condensing unit is installed outdoors (which allows the

condenser to be exposed to low ambient temperatures), the

condenser fan may cycle on and off. The purpose of the fan

cycling is to maintain the system high side pressure, which

will ensure an adequate refrigeration process. The fan cycling

process is accomplished by way of a Johnson Control or fan

cycling switch attached to the condensing unit.

Bottle Probe Failure Protection

In the event that a bottle probe should fail, the APST (Advance

Product Safety Technology) will automatically transition the

refrigeration compressor cycles to a pre-determined time

series (based on detailed laboratory testing), which will ensure

that the product is kept within the safe range.

Display

The bottle probe temperature is displayed by default. “Def”

is displayed during Anti-Frost. The air sensing probe and

evaporator probe temperatures can be accessed by pushing

the SET button and scrolling through “PB1” (bottle probe), and

“PB2” (evaporator probe).

Safety Features

Once the cellar has reached the proper Set temperature,

the compressor goes into its pump down cycle. When the

compressor turns off the delay on break timer prevents the

compressor from short cycling.

In the event of a faulty bottle probe, the compressor will cycle

off for 10 minutes and on for 40 minutes. “E1” will be displayed

on the screen.

Alarms

See “Alarm Codes” in Controller Function chart.

Remote Control Panel (standard)

The remote keypad is designed to give the user the ability to

monitor and change cellar conditions when the evaporating

unit is placed in a remote location outside of the cellar.