Setpoints
55
Mode C
Setpoint with dribble control
Dribble control provides two-speed cutoff (fast or slow feed) to enhance accuracy. Cutoff occurs
when WT≥ SP – dr – Pr.
Use the following steps to set Mode C setpoint values.
1.
Press
SETPOINT 1
or
SETPOINT 2
on front panel.
2.
Enter desired setpoint value, (display times out if no number is entered for several
seconds).
3.
Press
ENT
. Display flashes number value alternated with dr.
4.
Enter desired dribble value, then press
ENT
key. Display returns to normal operation.
5.
The setpoint value can be recalled any time by pressing the appropriate setpoint twice.
SP1
SP1-Dr
SP2
SP2-dr
Mode D
Setpoint with preact and dribble control
Slow feed cutoff occurs when WT ≥ SP – Pr. Fast feed cutoff occurs when WT ≥ SP – Pr – dr.
Use the following steps to set Mode D setpoint values.
1.
Press
SETPOINT 1
or
SETPOINT 2
on front panel.
2.
Enter desired setpoint value, (display times out if no number is entered for several
seconds).
3.
Press
ENT
. Display flashes number value alternated with Pr.
4.
Enter the desired preact value; then press
ENT
key.
5.
Enter the desired dribble value; then press
ENT
key.
6.
The setpoint value can be recalled any time by pressing the appropriate setpoint twice for
preact and a third time for dribble value.
SP1-Pr
SP1-Pr-dr
SP2-Pr
SP2-Pr-dr
Mode
Description
Setpoint
100
90
80
70
60
50
40
30
20
10
0
SP1-dr
SP2
WEIGHT
MODE C
WIRE
PLACEMENT
TB3 - 5
TB3 - 4
TB3 - 3
TB3 - 2
SP1
SP2-dr
SP1-Pr
-dr
SP2-Pr
MODE D
WIRE
PLACEMENT
TB3 - 5
TB3 - 4
TB3 - 3
TB3 - 2
SP1-Pr
SP2-Pr
-dr
100
90
80
70
60
50
40
30
20
10
0
WEIGHT