Setpoints

75

8.3

Batch Operations

Softkeys can be conÞgured to allow operator control
of batch operations from the

920i

front panel (see

Figure 8-9), Softkeys can be conÞgured using

iRev

,

serial commands, or the FEATURE menu (see
Section 3.2.3 on page 34).

Figure 8-9. Batching Softkeys

Setpoint

Display or change assigned setpoints.

Batch Start

Starts batch process.

Batch Pause

Pauses an active batch. Processing is
suspended until

B a t c h S t a r t

is

pressed again.

Batch Reset

Stops and resets an active batch to the
beginning of the process.

Batch Stop

Stops an active batch and turns off all
associated digital outputs.

To prevent personal injury and equipment
damage, software-based interrupts must
always be supplemented by emergency
stop switches and other safety devices
necessary for the application.

Batching Switch

The batching switch option, PN 19369, comes as a
complete unit in an FRP enclosure, with legend plate,
locking stop switch (mushroom button), and a
run/start/abort 3-way switch.

Both switches are wired into the indicatorÕs digital I/O
terminal strip as shown in Figure 8-11. Each switch
uses a separate digital input.

Once cables and switches have been connected to the
indicator, use the setup switch to place the indicator in
setup mode. Use the DIG I/O menu (see Section 3.2.6
on page 42) to conÞgure digital input and output
functions.

Figure 8-10. Batching Switch

When conÞguration is complete, exit setup mode.
Initialize the batch by turning the 3-way switch to

ABORT

, then unlock the STOP button (the STOP

button must be in the OUT position to allow the batch
process to run). The batching switch is now ready to
use.

If no digital input is assigned to
BATRUN, batching proceeds as if
BATRUN were always on: the batch

will start when the 3-way switch is turned to RUN, but the
STOP mushroom button will not function.

Figure 8-11. Batching Switch Wiring Diagram Example

Warning

ABORT

START

RUN

EMERGENCY

STOP

IN-STOP

OUT-RUN

Warning

RED

WHITE

BLACK

RED

BLACK

STOP/START MUSHROOM SWITCH

ABORT/RUN/START SWITCH

A
B
O
R
T

S
T
A
R
T

34

3

4

34

1

2

2

1

NO

NC

NC

NO

NO

J2

+5VDC

GND

DIO1

DIO2

DIO3

DIO4

DIGITAL I/O

1

2

4

5

6

3

CPU BOARD