6table 1 — physical data (cont) – Carrier 48HJD005-007 User Manual
Page 6

6
Table 1 — Physical Data (cont)
LEGEND
*Single phase/three phase.
†Indicates automatic reset.
**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners.
48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005-
007 (150,000 Btuh Heat input) units have 3 burners.
††An LP kit is available as an accessory.
||Three-phase standard models have heating inputs as shown. Single-phase
standard models have one-stage heating with heating input values as follows:
48HJE004, 48HJD005,006 — 72,000 Btuh
48HJF004, 48HJE005,006 — 115,000 Btuh
48HJF005,006 — 150,000 Btuh
***California compliant three-phase models.
†††California SCAQMD compliant low NO
x
models have combustion products that
are controlled to 40 nanograms per joule or less.
BASE UNIT 48
HJE/F/H/K/M/N004
HJD/E/F/G/H/K/L/M/N005
HJD/E/F/G/H/K/L/M/N006
HJD/HJE/HJF007
FURNACE SECTION
Rollout Switch Cutout Temp (F)†
195
195
195
195
Burner Orifice Diameter (in. ...drill size)**
Natural Gas — Std
HJE .113...33
HJD .113...33
HJD .113...33
HJD .113...33
HJF .113...33
HJE .113...33
HJE .113...33
HJE .113...33
—
HJF .129...30
HJF .129...30
HJF .129...30
HJH .113...33
HJG .113...33
HJG .113...33
—
HJK .113...33
HJH .113...33
HJH .113...33
—
—
HJK .129...30
HJK .129...30
—
HJM .102...38
HJL .102...38
HJL .102...38
—
HJN .102...38
HJM .102...38
HJM .102...38
—
—
HJN .116...32
HJN .116...32
—
Liquid Propane — Alt††
HJE .089...43
HJD .089...43
HJD .089...43
HJD .089...43
HJF .089...43
HJE .089...43
HJE .089...43
HJE .089...43
—
HJF .102...38
HJF .102...38
HJF .102...38
HJH .082...45
HJG .089...43
HJG .089...43
—
HJK .082...45
HJH .089...43
HJH .089...43
—
—
HJK .102...38
HJK .102...38
—
HJM .082...45
HJL .082...45
HJL .082...45
—
HJN .082...45
HJM .082...45
HJM .082...45
—
—
HJN .094...42
HJN .094...42
—
Thermostat Heat Anticipator Setting (amps) 208/230/460 v
First Stage
.14
.14
.14
.14
Second Stage
.14
.14
.14
.14
Gas Input (Btuh)
First Stage/Second Stage
HJE|| 50,000/ 72,000
HJD|| 50,000/ 72,000
HJD|| 50,000/ 72,000
HJD|| 50,000/ 72,000
HJF|| 82,000/115,000
HJE|| 82,000/115,000
HJE|| 82,000/115,000
HJE|| 82,000/115,000
—
HJF|| 120,000/150,000
HJF|| 120,000/150,000
HJF|| 120,000/150,000
HJH*** —/ 72,000
HJG*** —/ 72,000
HJG*** —/ 72,000
—
HJK***—/115,000
HJH*** —/115,000
HJH*** —/115,000
—
—
HJK*** —/150,000
HJK*** —/150,000
—
HJM††† —/ 60,000
HJL††† —/ 60,000
HJL††† —/ 60,000
—
HJN††† —/ 90,000
HJM††† —/ 90,000
HJM†††—/ 90,000
—
—
HJN††† —/120,000
HJN††† —/120,000
—
Efficiency (Steady State) (%)
HJE 82
HJD 82
HJD 82
HJD 82
HJF 81
HJE 81
HJE 81
HJE 81
—
HJF 80
HJF 80
HJF 80
HJH 82
HJG 82
HJG 82
—
HJK 81
HJH 81
HJH 81
—
—
HJK 80
HJK 80
—
HJM 81
HJL 81
HJL 81
—
HJN 81
HJM 81
HJM 81
—
—
HJN 82
HJN 82
—
Temperature Rise Range
HJE 15-45
HJD 15-45
HJD 15-45
HJD 15-45
HJF 55-85
HJE 35-65
HJE 35-65
HJE 35-65
—
HJF 50-80
HJF 50-80
HJF 50-80
HJH 15-45
HJG 15-45
HJG 15-45
—
HJK 55-85
HJH 35-65
HJH 35-65
—
—
HJK 50-80
HJK 50-80
—
HJM 20-50
HJL 20-50
HJL 20-50
—
HJN 30-60
HJM 30-60
HJM 30-60
—
—
HJN 40-70
HJN 40-70
—
Manifold Pressure (in. wg)
Natural Gas — Std
3.5
3.5
3.5
3.5
Liquid Propane — Alt††
3.5
3.5
3.5
3.5
Maximum Static Pressure (in. wg)
1.0
1.0
1.0
1.0
Field Gas Connection Size (in.)
1
/
2
1
/
2
1
/
2
1
/
2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
450 ± 50
Cutout
428
Reset (Auto.)
320
LOSS-OF-CHARGE SWITCH/LOW-PRESSURE
SWITCH (Liquid LIne) (psig)
Cutout
7 ± 3
Reset (Auto.)
22 ± 5
FREEZE PROTECTION THERMOSTAT
Opens (F)
30 ± 5
Closes (F)
45 ± 5
OUTDOOR-AIR INLET SCREENS
Cleanable
Quantity...Size (in.)
1...20 x 24 x 1
RETURN-AIR FILTERS
Throwaway
Quantity...Size (in.)
2...16 x 25 x 2
Bhp — Brake Horsepower