Table 2C — 48HJ High-Static Motor Units Without Electrical Convenience Outlet

Table 2D — 48HJ High-Static Motor Units With Electrical Convenience Outlet

LEGEND

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

UNIT
48HJ

NOMINAL

VOLTAGE

(V-Ph-Hz)

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

IFM

COMBUSTION

FAN MOTOR

POWER

SUPPLY

MINIMUM UNIT

DISCONNECT

SIZE*

Min

Max

RLA

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

LRA

004

208/230-3-60

187

254

10.3

77.0

0.7

5.8

0.6

19.4/19.4

25/25

19/19

120/120

460-3-60

414

508

5.1

39.0

0.4

2.6

0.3

9.4

15

9

60

575-3-60

518

632

4.2

31.0

0.4

2.6

0.3

7.7

15

8

48

005

208/230-3-60

187

254

13.5

99.0

0.7

5.8

0.6

23.4/23.4

30/30

23/23

142/142

460-3-60

414

508

7.4

49.5

0.4

2.6

0.3

12.3

15

12

71

575-3-60

518

632

5.8

40.0

0.4

2.6

0.3

9.7

15

9

57

006

208/230-3-60

187

254

17.3

123.0

1.5

7.5

0.6

30.6/30.6

35/35

30/30

187/187

460-3-60

414

508

9.0

62.0

0.8

3.4

0.3

15.5

20

15

94

575-3-60

518

632

7.1

50.0

0.8

3.4

0.3

12.2

15

12

76

007

208/230-3-60

187

254

20.5

156.0

1.4

7.5

0.6

30.6/30.6

35/35

30/30

187/187

460-3-60

414

508

9.6

70.0

0.6

3.4

0.3

15.5

20

15

94

575-3-60

518

632

7.7

56.0

0.6

3.4

0.3

12.2

15

12

76

UNIT
48HJ

NOMINAL

VOLTAGE

(V-Ph-Hz)

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

IFM

COMBUSTION

FAN MOTOR

POWER

SUPPLY

MINIMUM UNIT

DISCONNECT

SIZE*

Min

Max

RLA

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

LRA

004

208/230-3-60

187

254

10.3

77.0

0.7

5.8

0.6

25.4/25.4

30/30

25

124/124

460-3-60

414

508

5.1

39.0

0.4

2.6

0.3

12.1

15

12

63

575-3-60

518

632

4.2

31.0

0.4

2.6

0.3

9.8

15

10

50

005

208/230-3-60

187

254

13.5

99.0

0.7

5.8

0.6

29.4/29.4

35/35

29

146/146

460-3-60

414

508

7.4

49.5

0.4

2.6

0.3

15.0

20

14

73

575-3-60

518

632

5.8

40.0

0.4

2.6

0.3

11.8

15

11

59

006

208/230-3-60

187

254

17.3

123.0

1.5

7.5

0.6

36.6/36.6

40/40

36

192/192

460-3-60

414

508

9.0

62.0

0.8

3.4

0.3

18.2

20

18

96

575-3-60

518

632

7.1

50.0

0.8

3.4

0.3

14.4

20

14

77

007

208/230-3-60

187

254

20.5

156.0

1.4

7.5

0.6

40.5/40.5

45/45

39

224/224

460-3-60

414

508

9.6

70.0

0.6

3.4

0.3

18.7

25

18

104

575-3-60

518

632

7.7

56.0

0.6

3.4

0.3

15.0

20

15

89

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA

Rated Load Amps

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

7
457