Table 2A — 48HJ Electrical Data Standard Motor (Units Without Electrical Convenience Outlet)

Table 2B — 48HJ Electrical Data Standard Motor (Units With Electrical Convenience Outlet)

LEGEND

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

UNIT
48HJ

NOMINAL

VOLTAGE

(V-Ph-Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

COMBUSTION

FAN MOTOR

POWER

SUPPLY

WITH OUTLET

MINIMUM UNIT

DISCONNECT

SIZE*

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP†

FLA

LRA

004

(3 Tons)

208/230-1-60

187

254

16.0

88.0

0.7

4.9

.57

25.6/25.6

35/35

25/25

101/101

208/230-3-60

187

254

10.3

77.0

0.7

4.9

.57

18.5/18.5

25/25

18/18

90/ 90

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

9.0

15

9

46

575-3-60

518

632

4.2

31.0

0.4

2.2

.30

7.3

15

7

36

005

(4 Tons)

208/230-1-60

187

254

23.7

129.0

0.7

4.9

.57

35.2/35.2

45/45

34/34

142/142

208/230-3-60

187

254

13.5

99.0

0.7

4.9

.57

22.5/22.5

30/30

22/22

112/112

460-3-60

414

508

7.4

49.5

0.4

2.2

.30

11.9

15

12

56

575-3-60

518

632

5.8

40.0

0.4

2.2

.30

9.3

15

9

45

006

(5 Tons)

208/230-1-60

187

254

28.8

169.0

1.5

8.8

.57

46.3/46.3

60/60

45/45

216/216

208/230-3-60

187

254

17.3

123.0

1.5

5.8

.57

28.9/28.9

35/35

28/28

168/168

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

14.7

20

14

84

575-3-60

518

632

7.1

50.0

0.8

2.6

.30

11.6

15

11

67

007

(6 Tons)

208/230-3-60

187

254

20.5

156.0

1.4

5.8

.57

32.8/32.8

40/40

32/32

200/200

460-3-60

414

508

9.6

70.0

0.6

2.6

.30

15.2

20

15

92

575-3-60

518

632

7.7

56.0

0.6

2.6

.30

12.2

15

13

78

UNIT
48HJ

NOMINAL

VOLTAGE

(V-Ph-Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

COMBUSTION

FAN MOTOR

POWER

SUPPLY

WITH OUTLET

MINIMUM UNIT

DISCONNECT

SIZE*

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP†

FLA

LRA

004

(3 Tons)

208/230-1-60

187

254

16.0

88.0

0.7

4.9

.57

31.6/31.6

40/40

30/30

106/106

208/230-3-60

187

254

10.3

77.0

0.7

4.9

.57

24.5/24.5

30/30

24/24

95/95

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

11.7

15

11

48

575-3-60

518

632

4.2

31.0

0.4

2.2

.30

9.5

15

9

38

005

(4 Tons)

208/230-1-60

187

254

23.7

129.0

0.7

4.9

.57

41.2/41.2

50/50

39/39

147/147

208/230-3-60

187

254

13.5

99.0

0.7

4.9

.57

28.5/28.5

35/35

27/27

117/117

460-3-60

414

508

7.4

49.5

0.4

2.2

.30

14.6

20

14

58

575-3-60

518

632

5.8

40.0

0.4

2.2

.30

11.5

15

11

47

006

(5 Tons)

208/230-1-60

187

254

28.8

169.0

1.5

8.8

.57

52.3/52.3

60/60

50/50

221/221

208/230-3-60

187

254

17.3

123.0

1.5

5.8

.57

34.9/34.9

40/40

34/34

173/173

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

17.4

20

17

86

575-3-60

518

632

7.1

50.0

0.8

2.6

.30

13.8

20

13

69

007

(6 Tons)

208/230-3-60

187

254

20.5

156.0

1.4

5.8

.57

38.8/38.8

45/45

37/37

205/205

460-3-60

414

508

9.6

70.0

0.6

2.6

.30

17.9

20

17

94

575-3-60

518

632

7.7

56.0

0.6

2.6

.30

14.3

20

15

79

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA

Rated Load Amps

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

7
457