Table 8 — Motor Nominal Horsepower
Table 9 — Outdoor Sound Power (Total Unit)
LEGEND
Table 10 — 48HJ004 Fan Performance — Vertical Discharge Units With Standard Motor
Table 11 — 48HJ004 Fan Performance — Vertical Discharge Units With High-Static Motor
LEGEND AND NOTES FOR TABLES 10 AND 11
LEGEND
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 2.)
2. Motor drive range is 760 to 1090 rpm for standard motor; 1075 to 1455
rpm for high-static motor. All other rpms require a field-supplied drive.
3. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 1.20 for standard motor, 2.40 for high-static
motor. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your
fan motors up to the ratings shown will not result in nuisance tripping
or premature motor failure. Unit warranty will not be affected. See
Evaporator-Fan Motor Data tables on page 20 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
6. Interpolation is permissible. Do not extrapolate.
UNIT 48HJ
MOTOR
NOMINAL HORSEPOWER
004
All
1.00
005
All
1.00
006
Single Phase
1.50
Three Phase
2.00
007
All
2.00
UNIT
48HJ
ARI
RATING
(Bels)
OCTAVE BANDS
63
125
250
500
1000
2000
4000
8000
004,005
7.6
55.9
66.0
64.0
66.2
68.4
64.5
61.7
57.3
006,007
8.0
59.1
68.9
68.7
71.9
74.0
68.9
65.7
59.0
ARI
— Air Conditioning and Refrigeration Institute
Bels — Sound Levels (1 bel = 10 decibels)
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
900
581
0.12
673
0.18
736
0.22
805
0.25
865
0.29
911
0.34
1000
644
0.19
709
0.22
782
0.28
835
0.30
900
0.35
937
0.38
1100
687
0.22
746
0.26
806
0.30
867
0.35
929
0.40
964
0.40
1200
733
0.26
785
0.32
843
0.35
903
0.41
960
0.47
994
0.50
1300
754
0.29
826
0.38
891
0.43
942
0.48
991
0.53
1047
0.60
1400
810
0.35
868
0.45
937
0.51
984
0.57
1032
0.62
1067
0.67
1500
841
0.42
911
0.53
985
0.61
1029
0.66
1073
0.72
1109
0.77
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.7
0.8
0.9
1.0
1.1
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
900
957
0.39
988
0.43
1039
0.47
1061
0.51
1083
0.54
1105
0.58
1000
992
0.44
1039
0.49
1061
0.55
1088
0.60
1111
0.66
1136
0.72
1100
1013
0.49
1068
0.55
1091
0.61
1109
0.66
1127
0.73
1145
0.80
1200
1045
0.56
1090
0.64
1109
0.68
1156
0.73
1203
0.81
1250
0.86
1300
1075
0.64
1122
0.70
1152
0.76
1190
0.82
1228
0.87
1266
0.94
1400
1110
0.73
1160
0.78
1181
0.83
1237
0.88
1293
0.94
1349
0.99
1500
1150
0.78
1190
0.84
1225
0.89
1271
0.95
1371
1.00
1383
1.05
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
900
673
0.18
805
0.25
911
0.34
988
0.43
1061
0.47
1000
709
0.22
835
0.30
937
0.38
1039
0.49
1086
0.55
1100
746
0.28
867
0.35
964
0.40
1068
0.55
1109
0.61
1200
785
0.32
903
0.41
994
0.50
1090
0.64
1156
0.68
1300
826
0.38
942
0.48
1047
0.60
1122
0.70
1190
0.76
1400
868
0.45
984
0.57
1087
0.67
1160
0.84
1237
0.85
1500
911
0.53
1029
0.66
1109
0.77
1190
1.00
1271
0.95
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
900
1105
0.57
1140
0.63
1170
0.68
1198
0.73
1224
0.77
1000
1136
0.63
1172
0.69
1203
0.75
1232
0.80
1258
0.86
1100
1145
0.67
1181
0.73
1213
0.80
1242
0.85
1268
0.91
1200
1210
0.74
1248
0.81
1282
0.88
1312
0.94
1340
1.01
1300
1266
0.84
1306
0.92
1341
1.00
1373
1.07
1402
1.14
1400
1349
0.93
1391
1.02
1429
1.11
1463
1.19
1494
1.26
1500
1363
1.05
1406
1.15
1465
1.25
1500
1.34
1532
1.43
Bhp
—
Brake Horsepower Input to Fan
FIOP
—
Factory-Installed Option