Table 14 — 48HJ006 Fan Performance — Vertical Discharge Units With Standard Motor
Single-Phase Units
3-Phase Units
Table 15 — 48HJ006 Fan Performance — Vertical Discharge Units With High-Static Motor
LEGEND AND NOTES FOR TABLES 14 AND 15
L
EGEND
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2.
indicates field-supplied motor and drive required.
3. Motor drive range is 1020 to 1460 rpm for single-phase standard
motors, 1120 to 1585 for 3-phase standard motors, and 1300 to 1685 for
high-static motors. All other rpms require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 1.30 for single-phase standard motors, 2.40
for 3-phase standard motors, and 2.90 for high-static motors. Extensive
motor and electrical testing on these units ensures that the full range of
the motor can be utilized with confidence. Using your fan motors up to
the ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor
Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
771
0.37
828
0.44
935
0.58
1027
0.73
1107
0.88
1185
1.04
1257
1.20
1330
1.38
1411
1.59
1600
816
0.45
869
0.51
968
0.66
1056
0.81
1127
0.97
1215
1.14
1286
1.31
1353
1.49
1421
1.68
1700
902
0.61
940
0.60
1007
0.75
1094
0.91
1175
1.09
1245
1.26
1315
1.44
1381
1.52
1443
1.69
1800
942
0.70
978
0.66
1063
0.82
1147
0.97
1248
1.20
1322
1.33
1395
1.46
1475
1.56
1542
1.71
1900
982
0.80
1023
0.78
1097
0.91
1175
1.11
1266
1.29
1356
1.47
1430
1.58
1504
1.69
1556
1.82
2000
1022
0.91
1068
0.90
1132
1.01
1218
1.23
1303
1.41
1397
1.52
1459
1.67
1532
1.82
1588
1.97
2100
1063
0.99
1115
1.00
1180
1.17
1261
1.35
1340
1.53
1428
1.66
1489
1.80
1567
1.99
1626
2.16
2200
1104
1.13
1159
1.15
1214
1.28
1310
1.52
1375
1.63
1459
1.80
1528
1.95
1603
2.17
1666
2.37
2300
1130
1.26
1202
1.29
1248
1.38
1358
1.69
1410
1.72
1488
1.93
1561
2.13
1637
2.35
1710
2.54
2400
1174
1.37
1237
1.41
1292
1.55
1392
1.81
1460
1.90
1532
2.14
1584
2.28
1671
2.55
1756
2.70
2500
1201
1.48
1272
1.53
1335
1.71
1427
1.94
1518
2.16
1575
2.35
1633
2.53
1698
2.72
—
—
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
771
0.37
828
0.44
935
0.58
1027
0.73
1107
0.88
1185
1.04
1257
1.20
1330
1.38
1411
1.59
1600
816
0.45
869
0.51
968
0.66
1056
0.81
1127
0.97
1215
1.14
1286
1.31
1353
1.49
1421
1.68
1700
902
0.61
940
0.60
1007
0.75
1094
0.91
1175
1.09
1245
1.26
1315
1.44
1381
1.52
1443
1.69
1800
942
0.70
978
0.66
1063
0.82
1147
0.97
1248
1.20
1322
1.33
1395
1.46
1475
1.56
1542
1.71
1900
982
0.80
1023
0.78
1097
0.91
1175
1.11
1266
1.29
1356
1.47
1430
1.58
1504
1.69
1556
1.82
2000
1022
0.91
1068
0.90
1132
1.01
1218
1.23
1303
1.41
1397
1.52
1459
1.67
1532
1.82
1588
1.97
2100
1063
0.99
1115
1.00
1180
1.17
1261
1.35
1340
1.53
1428
1.66
1489
1.80
1567
1.99
1626
2.16
2200
1104
1.13
1159
1.15
1214
1.28
1310
1.52
1375
1.63
1459
1.80
1528
1.95
1603
2.17
1666
2.37
2300
1130
1.26
1202
1.29
1248
1.38
1358
1.69
1410
1.72
1488
1.93
1561
2.13
1637
2.35
1710
2.54
2400
1174
1.37
1237
1.41
1292
1.55
1392
1.81
1460
1.90
1532
2.14
1584
2.28
1671
2.55
1756
2.70
2500
1201
1.48
1272
1.53
1335
1.71
1427
1.94
1518
2.16
1575
2.35
1633
2.53
1698
2.72
—
—
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
808
0.42
914
0.56
1001
0.69
1084
0.85
1168
1.01
1600
846
0.49
950
0.64
1034
0.78
1111
0.94
1194
1.11
1700
884
0.57
983
0.72
1068
0.88
1145
1.03
1218
1.21
1800
924
0.66
1018
0.82
1105
0.98
1179
1.13
1246
1.32
1900
965
0.76
1057
0.92
1143
1.10
1212
1.26
1280
1.43
2000
1008
0.87
1096
1.04
1177
1.22
1247
1.40
1300
1.57
2100
1051
0.99
1136
1.17
1210
1.35
1284
1.54
1347
1.72
2200
1095
1.12
1173
1.30
1245
1.49
1322
1.70
1380
1.89
2300
1140
1.26
1210
1.47
1284
1.65
1356
1.80
1418
2.07
2400
1185
1.41
1249
1.61
1323
1.80
1389
2.03
1456
2.26
2500
1231
1.57
1289
1.78
1363
2.00
1424
2.22
1500
2.45
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
1199
1.19
1126
1.46
1250
1.69
1301
1.91
1349
2.12
1600
1263
1.28
1275
1.49
1299
1.78
1352
2.01
1401
2.23
1700
1295
1.39
1351
1.58
1352
1.80
1407
2.03
1459
2.26
1800
1319
1.52
1389
1.71
1435
1.91
1494
2.15
1548
2.40
1900
1343
1.64
1415
1.80
1478
2.05
1538
2.31
1594
2.57
2000
1374
1.77
1438
1.99
1505
2.21
1566
2.49
1624
2.77
2100
1409
1.91
1465
2.14
1533
2.45
1596
2.77
1654
3.08
2200
1442
2.08
1498
2.30
1568
2.64
1632
2.97
1691
3.31
2300
1475
2.26
1554
2.64
1627
3.03
1693
3.42
1755
3.81
2400
1565
2.47
1649
2.89
1726
3.31
—
—
—
—
2500
1596
2.95
1682
3.45
1760
3.96
—
—
—
—
Bhp
—
Brake Horsepower Input to Fan
FIOP
—
Factory-Installed Option