beautypg.com

5table 1 — physical data – Carrier 48HJD005-007 User Manual

Page 5

background image

5

Table 1 — Physical Data

LEGEND

*Single phase/three phase.

†Indicates automatic reset.

**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners.

48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005-
007 (150,000 Btuh Heat input) units have 3 burners.

††An LP kit is available as an accessory.

||Three-phase standard models have heating inputs as shown. Single-phase

standard models have one-stage heating with heating input values as follows:

48HJE004, 48HJD005,006 — 72,000 Btuh
48HJF004, 48HJE005,006 — 115,000 Btuh
48HJF005,006 — 150,000 Btuh

***California compliant three-phase models.

†††California SCAQMD compliant low NO

x

models have combustion products that

are controlled to 40 nanograms per joule or less.

BASE UNIT 48

HJE/F/H/K/M/N004

HJD/E/F/G/H/K/L/M/N005

HJD/E/F/G/H/K/L/M/N006

HJD/HJE/HJF007

NOMINAL CAPACITY

3

4

5

6

OPERATING WEIGHT (lb)

Unit

530

540

560

615

With Durablade Economizer

564

574

594

649

With EconoMi$er

577

587

607

662

With MoistureMiser Dehumidification Package

548

558

578

633

Roof Curb

115

115

115

115

COMPRESSOR

Scroll

Quantity

1

1

1

1

Oil (oz)

42

53

50

60

REFRIGERANT TYPE

R-22

Operating Charge (lb-oz)
Standard Unit

5- 8

8-6

10- 0

9-10

Unit With MoistureMizer Dehumidification Package

8-13

11-2

12-13

13- 6

CONDENSER FAN

Propeller

Quantity...Diameter (in.)

1...22

1...22

1..22

1...22

Nominal Cfm

3500

3500

4100

4100

Motor Hp...Rpm

1

/

4

...825

1

/

4

...825

1

/

4

...1100

1

/

4

...1100

Watts Input (Total)

180

180

320

320

CONDENSER COIL

Enhanced Copper Tubes, Aluminum Lanced Fins

Standard Unit

Rows...Fins/in.

1...17

2..17

2...17

2...17

Total Face Area (sq ft)

14.6

16.5

16.5

16.5

Unit with MoistureMiser Dehumidification Package

Rows...Fins/in.

1...17

1...17

1...17

1...17

Total Face Area (sq ft)

3.9

3.9

3.9

3.9

EVAPORATOR FAN

Centrifugal Type, Belt Drive

Quantity...Size (in.)

1...10 x 10

1...10 x 10

1...10 x 10

1...10 x 10

Nominal Cfm

1200

1600

2000

2400

Maximum Continuous Bhp

Std

1.20

1.20

1.30/2.40*

2.40

Hi-Static

2.40

2.40

2.90

2.90

Motor Frame Size

Std

48

48

48/56*

56

Hi-Static

56

56

56

56

Fan Rpm Range

Std

760-1090

840-1185

1020-1460/1120-1585*

1120-1585

Hi-Static

1075-1455

1075-1455

1300-1685

1300-1685

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Fan Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter

A/B (in.)

Std

1.9/2.9

1.9/2.0

2.4/3.4

2.4/3.4

Hi-Static

2.8/3.8

2.8/3.8

3.4/4.4

3.4/3.4

Nominal Motor Shaft Diameter (in.)

Std

1

/

2

1

/

2

5

/

8

5

/

8

Hi-Static

5

/

8

5

/

8

5

/

8

5

/

8

Fan Pulley Pitch Diameter (in.)

Std

4.5

4.0

4.0

4.0

Hi-Static

4.5

4.0

4.5

4.5

Belt — Type...Length (in.)

Std

1...A...33

1...A...33

1....4...40

1...A...38

Hi-Static

1...A...39

1...A...39

1...A...40

1...A...40

Pulley Center Line Distance (in.)

10.0-12.4

10.0-12.4

14.7-15.5

14.7-15.5

Speed Change per Full Turn of

Movable Pulley Flange (rpm)

Std

65

70

75

95

Hi-Static

65

65

60

60

Movable Pulley Maximum Full

Turns from Closed Position

Std

5

5

6

5

Hi-Static

6

6

5

5

Factory Setting — Full Turns Open

Std

3

3

3

3

Hi-Static

3

1

/

2

3

1

/

2

3

1

/

2

3

1

/

2

Factory Speed Setting (rpm)

Std

890

980

1240

1304

Hi-Static

1233

1233

1396

1396

Fan Shaft Diameter at Pulley (in.)

5

/

8

5

/

8

5

/

8

5

/

8

EVAPORATOR COIL

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Metering Device

Rows...Fins/in.

2...15

2...15

4...15

4...15

Total Face Area (sq ft)

5.5

5.5

5.5

5.5

Bhp — Brake Horsepower