Carrier 48HJD005-007 User Manual
Page 24

24
Table 16 — 48HJ007 Fan Performance — Vertical Discharge Units With Standard Motor
Table 17 — 48HJ007 Fan Performance — Vertical Discharge Units With High-Static Motor
LEGEND AND NOTES FOR TABLES 16 AND 17
LEGEND
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2.
indicates field-supplied motor and drive required.
3. Motor drive range is 1120 to 1585 rpm for standard motors, 1130 to
1685 rpm for high-static motors. All other rpms require a field-supplied
drive.
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 2.40 for standard motors, 2.90 for high-
static motors. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confidence.
Using your fan motors up to the ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
See Evaporator-Fan Motor Data tables on page 20 for additional infor-
mation.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1800
942
0.70
978
0.66
1063
0.82
1147
0.97
1248
1.20
1322
1.33
1395
1.46
1475
1.56
1542
1.71
1900
982
0.80
1023
0.78
1097
0.91
1175
1.11
1266
1.29
1356
1.47
1430
1.58
1504
1.69
1556
1.82
2000
1022
0.91
1068
0.90
1132
1.01
1218
1.23
1303
1.41
1397
1.52
1459
1.67
1532
1.82
1588
1.97
2100
1063
0.99
1115
1.00
1180
1.17
1261
1.35
1340
1.53
1428
1.66
1489
1.80
1567
1.99
1626
2.16
2200
1104
1.13
1159
1.15
1214
1.28
1310
1.52
1375
1.63
1459
1.80
1528
1.95
1603
2.17
1666
2.37
2300
1130
1.26
1202
1.29
1248
1.38
1358
1.69
1410
1.72
1488
1.93
1561
2.13
1637
2.35
1710
2.54
2400
1174
1.37
1237
1.41
1292
1.55
1392
1.81
1460
1.90
1532
2.14
1584
2.28
1671
2.55
1756
2.70
2500
1201
1.48
1272
1.53
1335
1.71
1427
1.94
1518
2.16
1575
2.35
1633
2.53
1698
2.72
—
—
2600
1246
1.62
1320
1.68
1368
1.81
1458
2.06
1562
2.42
1620
2.59
1675
2.77
—
—
—
—
2700
1285
1.75
1361
1.82
1400
1.91
1490
2.19
1602
2.64
1666
2.85
—
—
—
—
—
—
2800
1304
1.87
1402
1.95
1439
2.08
1543
2.43
1642
2.86
—
—
—
—
—
—
—
—
2900
1345
2.07
1446
2.16
1477
2.16
1585
2.65
—
—
—
—
—
—
—
—
—
—
3000
1378
2.26
1489
2.36
1529
2.52
1598
2.73
—
—
—
—
—
—
—
—
—
—
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1800
978
0.66
1063
0.82
1147
0.97
1248
1.20
1322
1.33
1900
1023
0.78
1097
0.91
1175
1.11
1266
1.29
1356
1.47
2000
1068
0.90
1132
1.01
1218
1.23
1303
1.41
1397
1.52
2100
1115
1.00
1180
1.17
1261
1.35
1340
1.53
1428
1.66
2200
1159
1.15
1214
1.28
1310
1.52
1375
1.63
1459
1.80
2300
1202
1.29
1248
1.38
1358
1.69
1410
1.72
1488
1.93
2400
1237
1.41
1292
1.55
1392
1.81
1460
1.90
1532
2.14
2500
1272
1.53
1335
1.71
1427
1.94
1518
2.16
1575
2.35
2600
1320
1.68
1368
1.81
1458
2.06
1562
2.42
1620
2.59
2700
1361
1.82
1400
1.91
1490
2.19
1602
2.64
1666
2.85
2800
1402
1.95
1439
2.08
1543
2.43
1642
2.86
1775
3.62
2900
1446
2.16
1477
2.16
1585
2.65
1753
3.58
—
—
3000
1489
2.36
1529
2.52
1598
2.73
1767
3.69
—
—
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1800
1395
1.46
1475
1.56
1542
1.71
1607
1.94
1667
2.16
1900
1430
1.58
1504
1.69
1556
1.82
1621
2.06
1682
2.30
2000
1459
1.67
1532
1.82
1588
1.97
1655
2.23
1717
2.49
2100
1489
1.80
1567
1.99
1626
2.16
1694
2.44
1758
2.73
2200
1528
1.95
1603
2.17
1666
2.37
1736
2.68
—
—
2300
1561
2.13
1637
2.35
1710
2.54
1782
2.87
—
—
2400
1584
2.28
1671
2.55
1756
2.70
—
—
—
—
2500
1633
2.53
1698
2.72
1779
3.13
—
—
—
—
2600
1675
2.77
1768
3.26
—
—
—
—
—
—
2700
1776
3.45
—
—
—
—
—
—
—
—
2800
—
—
—
—
—
—
—
—
—
—
2900
—
—
—
—
—
—
—
—
—
—
3000
—
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower Input to Fan
FIOP
—
Factory-Installed Option