Carrier 48HJD005-007 User Manual
Page 22
22
Table 12 — 48HJ005 Fan Performance — Vertical Discharge Units With Standard Motor
Table 13 — 48HJ005 Fan Performance — Vertical Discharge Units With High-Static Motor
LEGEND AND NOTES FOR TABLES 12 AND 13
LEGEND
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2.
indicates field-supplied motor and drive required.
3. Motor drive range is 840 to 1185 rpm for standard motor; 1075 to
1455 rpm for high-static motor. All other rpms require a field-supplied
drive.
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 1.2 for standard motor, 2.4 for high-static
motor. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your
fan motors up to the ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See Evapora-
tor-Fan Motor Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1
0.2
0.3
0.4
0.6
0.7
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1200
596
0.20
665
0.25
722
0.31
779
0.36
872
0.48
915
0.54
957
0.60
1300
633
0.24
699
0.30
754
0.36
809
0.42
902
0.55
943
0.61
984
0.67
1400
672
0.30
735
0.36
788
0.42
840
0.48
933
0.62
972
0.69
1011
0.75
1500
711
0.35
770
0.42
822
0.49
873
0.55
963
0.69
1002
0.77
1041
0.84
1600
751
0.42
835
0.49
871
0.56
907
0.63
993
0.77
1033
0.85
1072
0.93
1700
791
0.49
873
0.57
907
0.65
941
0.72
1024
0.87
1064
0.96
1103
1.04
1800
831
0.58
881
0.66
929
0.74
976
0.81
1057
0.97
1095
1.06
1132
1.14
1900
872
0.67
919
0.75
965
0.84
1011
0.92
1091
1.08
1127
1.17
1162
1.25
2000
913
0.77
958
0.86
1002
0.95
1046
1.03
1125
1.21
1160
1.30
1195
1.38
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.9
1.0
1.1
1.2
1.4
1.6
1.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1200
993
0.65
1028
0.69
1056
0.72
1083
0.74
1134
0.80
1185
0.88
1331
0.99
1300
1021
0.74
1058
0.80
1090
0.85
1121
0.89
1171
0.94
1219
1.00
1268
1.10
1400
1049
0.82
1086
0.89
1120
0.96
1153
1.00
1210
1.12
1257
1.17
1307
1.25
1500
1077
0.92
1113
0.99
1147
1.06
1180
1.13
1241
1.27
1295
1.37
1339
1.43
1600
1107
1.00
1141
1.09
1174
1.17
1207
1.25
1269
1.40
1326
1.54
1376
1.65
1700
1137
1.12
1171
1.20
1203
1.29
1235
1.37
1296
1.53
1354
1.70
1407
1.84
1800
1167
1.23
1202
1.32
1233
1.41
1263
1.49
1323
1.67
1381
1.85
1436
2.02
1900
1197
1.35
1232
1.45
1263
1.54
1294
1.63
1351
1.81
1408
2.00
1463
2.19
2000
1229
1.48
1262
1.58
1294
1.68
1325
1.78
1362
1.97
1436
2.16
1489
2.36
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1200
665
0.25
779
0.36
872
0.48
957
0.60
1028
0.69
1300
699
0.30
809
0.42
902
0.55
984
0.67
1058
0.80
1400
735
0.36
840
0.48
933
0.62
1011
0.75
1086
0.89
1500
770
0.42
873
0.55
963
0.69
1041
0.84
1113
0.99
1600
835
0.49
907
0.63
993
0.77
1072
0.93
1141
1.09
1700
873
0.57
941
0.72
1024
0.87
1103
1.04
1171
1.20
1800
881
0.66
976
0.81
1057
0.97
1132
1.14
1202
1.32
1900
919
0.75
1011
0.92
1091
1.08
1162
1.25
1232
1.45
2000
958
0.86
1046
1.03
1125
1.21
1195
1.38
1262
1.58
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1200
1083
0.74
1134
0.80
1185
0.88
1331
0.99
1374
1.09
1300
1121
0.89
1171
0.94
1219
1.00
1268
1.10
1309
1.21
1400
1153
1.00
1210
1.12
1257
1.17
1307
1.25
1349
1.37
1500
1180
1.13
1241
1.27
1295
1.37
1339
1.43
1382
1.57
1600
1207
1.25
1269
1.40
1326
1.54
1376
1.65
1420
1.81
1700
1235
1.37
1296
1.53
1354
1.70
1407
1.84
1452
2.02
1800
1263
1.49
1323
1.67
1381
1.85
1436
2.02
1482
2.22
1900
1294
1.63
1351
1.81
1408
2.00
1463
2.19
—
—
2000
1325
1.78
1362
1.97
1436
2.16
1489
2.36
—
—
Bhp
—
Brake Horsepower Input to Fan
FIOP
—
Factory-Installed Option