The key cylinder arming switch must be set to "OFF". To prevent the alarm
from sounding during installation, attach battery AFTER main power is
applied.
Delayed Egress Device requires a connection to the Fire Alarm System.
The fire alarm connection needs to be made
Externally at the Power Supply.
During a fire alarm condition the delayed egress will be deactivated.
MAIN POWER CONNECTION: (1 AND 2)
See Power Supply instructions
DETEX REQUIRES USING THE FIRE ALARM
CONNECTION IN THE POWER SUPPLY:
CLOSED
connection is provided to the fire alarm system when not
in-alarm and OPEN when in-alarm. See power supply instructions
for details.
REMOTE BY-PASS: (5 & 6)
Normally open (N.O.)
When the contact is closed momentarily, the door can be opened
without the alarm sounding. The unit will automatically re-arm in
15 seconds after the door is closed (three quick audible beeps).
BY-PASS RELAY: (7, 8 & 9)
Dry contact output.
The BY-PASS relay is energized when the unit is disarmed by
the KEY or REMOTE BY-PASS to indicate to a remote indicator
that the door is not armed.
ALARM RELAY: (10, 11 & 12)
Dry contact output.
The ALARM relay is energized when the unit is sounding its alarm to indicate
to a remote indicator that an unauthorized exit has been attempted.
OUTSIDE KEY CONTROL
If the OKC option is used, the outside
key bypasses and rearms the alarm.
STATUS INDICATOR (SLIDE SWITCH)
ON: Green LED blinks every three seconds
when the unit is disarmed.
Red LED blinks every three seconds
when the unit is armed.
OFF: No status indication
POWER REQUIREMENT:
.4 AMPS @ 24 VDC
Orange/Blue to magnet
Factory
installed
jumper
Terminal Block
9V Alkaline
Battery
Removable
Dis Lo Bat switch:
To disable the low-battery
indication, slide "DisLoBat"
switch to 'ON'
+RED
-BLK
OBSERVE
POLARITY
24VDC
POWER SUPPLY
RED +24V
BLACK GROUND
Status
indicator switch
1 2 3 4 5 6 7 8 9 10 1112
EM ELECTRICAL OPTIONS
L9=Less 9V Battery
SI= Status indicator
WIRING DIAGRAM A
1 2
104878 Page 4