Ac-powered routers – Cisco XR 12410 User Manual
Page 64

Chapter 2 Preparing for Installation
Site Requirement Guidelines
2-14
Cisco XR 12410 and Cisco XR 12810 Router Installation Guide
OL-17441-01
AC-Powered Routers
AC PEMs operate in the nominal range of 200 VAC to 240 VAC and require a
minimum service of:
•
20 A for operation in North America
•
16 A for international operation
•
13 A for operation in the UK
Each of the AC power inputs requires separate dedicated branch circuit. For a list
of the nominal and acceptable value ranges for source AC power, refer to
shows the different styles of AC power cords used to connect to the
local AC power source that are available for North America and various locales.
Figure 2-7
AC Power Cord Plugs and Appliance Coupler
26044
North America
Rewirable twist-lock plug
NEMA L6-20P (20A)
Australia, New Zealand
SAA/3 plug
AS/NZZS 3112-1993 (15A)
Europe, Argentine, Brazil
VIIG plug
CEE (7) VII (16A)
Appliance coupler
C19W coupler
Hot EN60320/C19 (20A)
Italy
1/3/16 plug
CEI 23-16 (16A)
United Kingdom
BS89/13
BS 1363/A
(13A; replaceable fuse)