Problem identification procedures, For rpz assemblies – Ames Fire & Waterworks 5000RPDA Reduced Pressure Detector Assemblies User Manual
Page 7

7
PROBLEM CAUSE
SOLUTION
C. Differential pressure relief
Differential pressure across
Repair shutoff valves
valve does not open
No. 1 check valve stays
during test
above 2psi due to
leaking outlet gate valve
Weak or broken relief
Disassemble and replace
valve spring
relief valve spring
Seat tube bound in
Disassemble and repair
body
O-ring
Plugged hydraulic hose
Disassemble and clean
D. Pressure relief valve -
Debris on sealing
Remove relief valve and
does not close
surface
clean
Plugged hydraulic
Disassemble and clean
hose
Damaged mounting seat gasket
Remove relief valve assembly
or seat tube
and replace
Ruptured diaphragm
Disassemble and replace
diaphragm
Damaged O-ring
Disassemble and replace
PROBLEM IDENTIFICATION PROCEDURES -
FOR RPZ ASSEMBLIES
SERIES 4000RP AND 5000RPDA
PROBLEM: Continuous or intermittent discharge from relief valve.
1. When using differential pressure gauge
2. Without using differential pressure gauge.
A. Check differential across No. 1 check valve
A. Close gate valve No. 2
Reading Problem
Result Problem
2 to 3 PSID
Leak in No. 1 or No. 2 check valve
If discharge stops
Leak in No. 2 check valve
4 to 7 PSID and steady Malfunctioning pressure relief valve
If discharge does
Go to B
not
stop
2 to 7 PSID fl uctuating Inlet pressure fl uctuating
B. Open No. 4 test cock to product a fl ow greater
than differential relief valve discharge
Result Problem
If discharge stops
Leak in No. 1 check valve
If discharge does
Malfunctioning pressure
not stop
relief valve