Problem identification procedures, For rpz assemblies – Ames Fire & Waterworks 5000RPDA Reduced Pressure Detector Assemblies User Manual

Page 7

background image

7

PROBLEM CAUSE

SOLUTION

C. Differential pressure relief

Differential pressure across

Repair shutoff valves

valve does not open

No. 1 check valve stays

during test

above 2psi due to

leaking outlet gate valve

Weak or broken relief

Disassemble and replace

valve spring

relief valve spring

Seat tube bound in

Disassemble and repair

body

O-ring

Plugged hydraulic hose

Disassemble and clean

D. Pressure relief valve -

Debris on sealing

Remove relief valve and

does not close

surface

clean

Plugged hydraulic

Disassemble and clean

hose

Damaged mounting seat gasket

Remove relief valve assembly

or seat tube

and replace

Ruptured diaphragm

Disassemble and replace

diaphragm

Damaged O-ring

Disassemble and replace

PROBLEM IDENTIFICATION PROCEDURES -

FOR RPZ ASSEMBLIES

SERIES 4000RP AND 5000RPDA

PROBLEM: Continuous or intermittent discharge from relief valve.

1. When using differential pressure gauge

2. Without using differential pressure gauge.

A. Check differential across No. 1 check valve

A. Close gate valve No. 2

Reading Problem

Result Problem

2 to 3 PSID

Leak in No. 1 or No. 2 check valve

If discharge stops

Leak in No. 2 check valve

4 to 7 PSID and steady Malfunctioning pressure relief valve

If discharge does

Go to B

not

stop

2 to 7 PSID fl uctuating Inlet pressure fl uctuating

B. Open No. 4 test cock to product a fl ow greater

than differential relief valve discharge

Result Problem

If discharge stops

Leak in No. 1 check valve

If discharge does

Malfunctioning pressure

not stop

relief valve