Ames Fire & Waterworks 950GS Stainless Steel Rate-of-Flow Control Valve User Manual
950 series, Rate-of-flow valve, Model
01/06
950 Series
Model
8550 Hansen Road
•
Houston, Texas 77075
•
(Ph) 713.943.0688
•
(Fx) 713.944.9445
•
www.amesfirewater.com
RATE-OF-FLOW VALVE
950
650
Operation
The AMES Model 950 / 650 Rate of Flow Control Valve is designed to automatically limit flow rate to a
constant, adjustable maximum. It is controlled by a normally open, differential control pilot designed to: 1)
Open (allowing fluid out of the main valve cover chamber) when the differential pressure across the orifice
plate is below the adjustable set point, and, 2) Close (allowing fluid to fill the main valve cover chamber) when
the differential pressure across the orifice plate is above the adjustable set point. A decrease in differential
pressure causes the valve to modulate towards an open position, increasing flow rate. An increase in
differential pressure causes the valve to modulate towards a closed position, decreasing flow rate.
The Orifice Plate Assembly should be installed three to five pipe diameters downstream of the Model
950 / 650, and field connected with 3/8” minimum copper tubing in accordance with factory piping
schematic. Please specify desired flow rate prior to ordering.
Installation Guidelines
• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid
installing valves 6” or large vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact
control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Install Orifice Plate Assembly (provided) 3 to 5 pipe diameters downstream of the 950 / 650 with the
sensing connections offset from top of pipeline to avoid air accumulation. The Orifice Plate Assembly
should not be installed next to a butterfly valve.
• Connect Orifice Plate Assembly to Rate-of-Flow Pilot using 3/8” diameter minimum copper tubing (field
installed) in accordance with factory piping schematic.
Other AMES Rate-of-Flow Control Valves
950-01 / 650-01
Rate-of-Flow Control Valve with Hydraulic Check Feature
950-15 / 650-15
Rate-of-Flow Control Valve with Solenoid (On-Off) Feature
951 / 651
Rate-of-Flow Control Valve with Pressure Reducing Feature
952 / 652
Rate-of-Flow Control Valve with Pressure Sustaining Feature