Ames Fire & Waterworks 3000B-FP Bronze Double Check Detector Assemblies with Gear Operated Slow Close Isolation Valves User Manual
Series afbv-fp, Slow close ball valve, Installation instructions
IS-A-AFBV-FP
Limited Warranty: Ames Fire & Waterworks (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date
of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting
from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no
control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights.
SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
Series AFBV-FP
Slow Close Ball Valve
Sizes:
3
⁄
4
" – 2" (20 – 50mm)
Installation Instructions
Series AFBV-FP are full-port bronze body ball valves that are UL/
FM rated for 175psi (12.1 bar) service in fire protection systems.
Available in threaded ends (NPT) with chrome-plated brass ball,
brass stem and PTFE seats for low torque and positive shut off.
Valve is designed for use with Schedule 40 copper pipe and is
approved for indoor and outdoor use.
Switch and Wiring
Supervisory Switch
The supervisory switch contains two, single pole, double throw,
pre-wired switches.
Supervisory Switch Wiring
Supervisory Switch Wiring
(1) Switches supervise valve in “open” position
(2) Switch 1 is intended for connection to the supervisory circuit
of a fire alarm control panel and has two 18 gauge wires per
terminal. Switch 2 is intended for auxiliary service and has one
18 gauge wire per terminal and may be connected to a remote
device such as a remote indicating light or audible bell.
Switch #1
S1
Normally Closed (NC):
(2) Blue
Normally Open (NO):
(2) Brown
Common (C):
(2) Yellow
Switch #2
S2
Normally Closed (NC): Blue with Orange Stripe
Normally Open (NO):
Brown with Orange Stripe
Common (C):
Yellow with Orange Stripe
Ground (G):
Green
The diagram shows a connection between the common terminal
(yellow-S1) and the normally closed terminal (blue-S1).
A similar connection is made between yellow-with-orange stripe-
S2 and blue-with-orange stripe-S2. With this configuration, an
indicator light or alarm would stay on until the valve is fully open.
When the valve is fully open, the indicator light and alarm will go
out. Any unused wires need to be capped off.
Connection of the valves internal supervisory switches are to be
made by qualified personnel in accordance with NFPA 72, National
Fire Alarm Code and NFPA 70, National Electrical Code.
RESISTIVE
LAMP
125 VAC
10.1A
1.5A
250 VAC
10.1A
1A
30 VDC
.4A
2A
250 VDC
0.2A
0.03A
Switches are rated
Bell
or
Horn
UL Listed
Junction Box
Conduit
N.C.
NO.
S1
S2
COM.
1
⁄
2
" NPT
Conduit Connectors
Wire Nuts
Fire Alarm Control
Panel Supervisory
Circuit
To End-of-Line Resistor,
or Next Indicator
Switch 1: 2 leads per terminal
Switch 2: 1 lead per terminal
Voltage Source
IS-A-AFBV-FP 1042