Baumer TA1220 User Manual
Page 22

TA1220
22
www.baumer.com
3.2 Inputs and outputs
Signal input
Specification
PNP
High level >2.6 V
Low level <2.4 V
Input resistance 1.5 kΩ
NPN
High level >2.6 V
Low level <2.4 V
Input resistance 3.9 kΩ
TTL
High level >2.6 V
Low level <2.4 V
NAMUR
Ion <1 mA, Ioff >3 mA
Input resistance 1.5 kΩ
Magnetic sensor
Vin >30 mVeff at 60 Hz
Vin >300 mVeff at 6 kHz
Contact
Input resistance 3.9 kΩ
Voltage 10...600 VAC
Measuring the frequency of the
voltage
Relay outputs (SET 1, SET 2)
Switching voltage max.
250 VAC / 110 VDC
Switching current max.
1 A
Switching performance max.
150 VA / 30 W
3.3 Voltage supply connection
There are several options for operation supply. Power supply must
be fed in via the recommended external fuse.
Operating voltage
External protection
85...265 VAC, (50/60 Hz) and 100...300 VDC
M 100 mA
21...53 VAC, (50/60 Hz) and 10.5...70 VDC
M 1 A