N.O.

7, Brown, Mag (

-

)

8, Yellow, Mag (+)

1584

Electromagnetic

Lock

Black (-)

Red (+)

24VDC 1.0AMP Regulated and Filtered Power Supply

110-120 VAC

Voltage adjust
for battery
backup

HOT

NEUT

GND

123

AC

F

Low voltage AC

From transformer

AC

DC DC

Output

Plug pigtail harness
connector into

8-pin

hinge connector at
frame side of door

NOTE: This drawing shows the
BPS Series. The PM Series
has no line voltage input, fuse
or connector to power on LED

2.5 AMP polyswitch breaker

Red

Black

Unconnected
terminal
for switch
hookup

Raceway harness with 8 & 4-pin

connectors. The 4-pin connector

is not used here.

Battery Pack

Red (+24), 2

Normally Closed Fire

Alarm Contact
(If Required)

Black (- Return), 1

Green (EG), 4

57- 80 Series Rail with 8 &

4-pin connectors The 4-pin

connector is not used here

Note: Typical raceway location is

shown. Other locations may exist

depending on door type

8
7

6
5

4
3

2
1

Pigtail harness
assembly with
8-pin connector

Wiring Notes:
1. Rail, raceway, electric hinge and

pigtail 8-pin connector terminations
and wire colors all match.

2. Tape or cap off ends of unused pigtail

wires (not shown) to ensure that they
do not short.

3. A fire alarm tie-in is required on fire

rated openings.

4. The fire alarm contact (when

required) must be wired to drop
24VDC power to rail. In this case,
terminate fire alarm contact
between the red (+ 24VDC) wire
and supply + 24VDC output.

System Wiring Examples

Sample Wiring #1 – Basic 57- Delayed Egress with Fire Alarm and Remote Reset

During a fire alarm condition, the fire alarm contact opens which de-energizes the rail magnet and allows

immediate egress.

Line voltage
fuse (1 AMP)

Electric hinge with
8-pin connectors

Blue (DS), 6

Connector

to power on LED

9

White, RR

15 1-800-810-WIRE • www.sargentlock.com • A7743C

Copyright © 2013, Sargen

t Manufacturing Company

, an A

SS

A AB

LO

Y G

roup company

. All right

s reser

ved

.

Reproductions in whole or in par

t without express writ

ten permission of Sargen

t Manufacturing Company is prohibited

.

04/15/13

57- Prefix 80 Series Exit Device