Appendix g, Ul data – Exide Technologies Section 94.20 User Manual
Page 96

APPENDIX G
92
UL DATA
CAUTION
To operate this charger from inputs other than 120 Vac, you must
use branch circuit protection. To reduce the risk of fire, use only
on circuits provided with the following branch circuit protection
in accordance with the National Electrical Code, ANSI/NFPA 70.
Charger Voltage Rating
Current
Rating
48 Vdc
130 Vdc
48 Vdc
130 Vdc
12 Adc
---
25A
---
20A
16 Adc
15A
25A
12A
20A
20 Adc
20A
30A
15A
30A
25 Adc
25A
40A
20A
35A
208 Vac Branch Circuit
Protection (Amperes)
240 Vac Branch Circuit
Protection (Amperes)
NOTE: This table does not apply to AT10.1 chargers with 480 Vac input.