Operating the at10.1 – Exide Technologies Section 94.20 User Manual
Page 28

OPERATING THE AT10.1
24
2. OPERATING THE AT10.1 BATTERY CHARGER
2.1. STARTING THE AT10.1
2.1.1. Understanding the startup sequence
The AT10.1 is set up at the factory to work with most common batteries 
and loads without further adjustment. When you start the AT10.1 for the 
first time, the factory settings (float voltage, equalize voltage, etc.) control 
the operation of the charger. You can change the settings after you start 
the charger. The FACTORY SETTINGS are shown in table on page 25. 
The AT10.1 startup routine takes about five seconds. The microprocessor 
that controls the AT10.1 initializes the charger by reading the settings that 
are stored internally. The control circuit then "soft starts" the charger, and 
the dc output voltage and current increase gradually to the rated value. 
2.1.2. Checking the installation
Be sure that you have followed the installation 
instructions carefully. Check the ac input 
supply voltage and the battery voltage, and be 
sure that they match the information on the 
AT10.1 nameplate. Verify that the jumpers on 
the main transformer T1 are correct for your 
ac supply voltage. Open the front panel, and 
check the battery polarity at the TB1 (+) and (-) 
terminals. 
2.1.3. Starting the AT10.1
When you are sure that all connections to the 
AT10.1 are properly made, follow these steps 
to start up the AT10.1: 
Using the Digital Meter
When you first start the 
AT10.1, the meter display 
alternates between dc output 
voltage and dc output current. 
Each reading is held for two 
seconds; lights to the left of 
the display indicate whether 
the meter is displaying 
voltage or current. 
If you want to "freeze" the 
meter to display only voltage, 
press the METER MODE 
key on the front panel. To 
freeze the meter to display 
only current, press the key 
again. Press the key twice 
more to revert to the 
alternating display.
• Turn on the front panel dc circuit breaker. The digital meter indicates the
battery voltage only. If the meter display doesn't light, do not proceed. 
Turn off the dc breaker, and check all connections and the battery 
polarity again. Also check the battery voltage. It must be above 50% of 
nominal voltage to turn on the display. If you can't find the problem, 
refer to the Troubleshooting Procedure in Section 3.1 on page 44. 
CAUTION: If you try to turn on the dc circuit breaker with the battery 
connected in reverse polarity, the circuit breaker will immediately 
trip. Do not try to close the dc breaker again, since this may damage 
the battery charger. Correct the battery polarity before proceeding. 
