Operating the at10.1, Suggested frequency: every 6 months – Exide Technologies Section 94.20 User Manual
Page 46

OPERATING THE AT10.1
42
SAMPLE PREVENTIVE MAINTENANCE PROCEDURE
AT10.1 BATTERY CHARGER
Suggested frequency: every 6 months
Maintenance date
Performed by
Step
(standard features)
Instructions Results
Clean battery 
charger 
• All vents clean and open. 
• Remove dust and debris from inside of 
unit.
OK
OK
Check all 
electrical 
connections 
and wiring 
• TB1 connections all tight. 
• Internal wiring connections tight, slip-on 
connectors fully seated. Wire and lug 
insulation in good condition. 
• Terminations at battery or bus are tight
and corrosion free.
OK
OK
 
 
OK
Check ac input 
voltage 
• Measure between TB1-L1 and TB1-L2
using an ac voltmeter. Value must be 
within +10%, -12% of nominal voltage. 
Input
Vac
Check dc 
output voltage 
• Measure at TB1(+) and TB1(-) using a dc
voltmeter. Value should agree with front 
panel voltmeter within 0.25%, and must 
be correct values for your battery. If the 
AT10.1 is using a temperature 
compensation probe, see the graph on 
page 23 to determine correct battery 
voltage. You need to know the battery 
temperature for this step. 
Float
Vdc
Equalize
Vdc
Check ripple 
voltage 
• Measure at battery terminals using an ac
voltmeter set to the milliVolts scale. 
Check against specification in Appendix 
A on page 70. 
Ripple
mVac
Test font panel 
indicators 
• Press
LAMP TEST
key on front panel.
OK
Test common 
alarm relay 
• Press
LAMP TEST
key and hold for 4
seconds. Common alarm relay will 
transfer. 
OK