beautypg.com

How to read the at10.1 model number, Group i ratings (6-25 adc), At10 x x – Exide Technologies Section 94.20 User Manual

Page 2

background image

HOW TO READ THE AT10.1 MODEL NUMBER

GROUP I RATINGS (6-25 Adc)


Your AT10.1 model number is coded to describe the options that are included. Please find the model
number on the data nameplate and write it in the spaces provided below. Then follow the chart to
determine the configuration of your battery charger.

AT10

X X

A

B

C D E F K L

M

N

P

Q

R

DESCRIPTION CODE FEATURE

DESCRIPTION CODE FEATURE

A

SERIES AT10

AT10.1

CHARGER

S

STANDARD

012

12 Vdc

M

MEDIUM AIC

024 24

Vdc

F

CIRCUIT
BREAKER
RATING
(SEE TABLE)

H HIGH

AIC

048 48

Vdc

B

NOMINAL
DC OUTPUT
VOLTAGE

130 130

Vdc

AUX SUPPLIED

006 6

Adc

K

AUX ALARM
RELAY BOARD

XXX NOT

SUPPLIED

012 12

Adc

016 16

Adc

G SUPPLIED

020 20

Adc

L

GROUND PAD

X NOT

SUPPLIED

C

NOMINAL
DC OUTPUT
CURRENT

025 25

Adc

U UNFILTERED

L SUPPLIED

F FILTERED

M

LIGHTNING
ARRESTOR

X NOT

SUPPLIED

D

FILTERING

E ELIMINATOR

120

120 Vac 60 Hz

1

F

APPLIED

208

208 Vac 60 Hz

1

N

FUNGUS
PROOFING

X NOT

APPLIED

240

240 Vac 60 Hz

1

S

APPLIED

480

480 Vac 60 Hz

2

P

STATIC
PROOFING

X NOT

APPLIED

220

220 Vac 50/60 Hz

3

380

380 Vac 50/60 Hz

3

Q

NOT USED

X

E

AC INPUT
VOLTAGE

416

416 Vac 50/60 Hz

3

R

NOT USED

X

DESCRIPTION CODE FEATURE

DESCRIPTION CODE FEATURE

1 - 120/208/240 Vac multi-tap input - Unit is wired and shipped from factory at specified voltage.
2 - 480 Vac input requires addition of medium or high ampere interrupting capacity circuit breakers.
3 - Special order, consult factory for availability.

INPUT AND OUTPUT CIRCUIT BREAKER INTERRUPTING RATINGS

CODE TYPE

AC RATINGS

(ALL INPUT VOLTAGES)

DC RATINGS

(125 Vdc)

S

STANDARD

240 Vac: 10,000 AIC

10,000 AIC

4

5,000 AIC

5

M MEDIUM

AIC

240 Vac: 25,000 AIC
480 Vac: 18,000 AIC

10,000 AIC

H HIGH

AIC

240 Vac: 65,000 AIC
480 Vac: 25,000 AIC

20,000 AIC

4 - Rating applies to 130Vdc 16-25 Adc units.

5 - Approximate rating applies to all other units.

NOTE

The model number listed on the charger data nameplate does not include any field-installed

options. Also, certain accessories are not included in the model number, even if they are shipped with the
charger. Check off below any accessories that were included, or that you install yourself.

floor/rack

mounting

brackets

analog ac voltmeter (penthouse-mounted)

NEMA-2 type drip shield assembly

analog ac ammeter (penthouse-mounted)

NEMA-4/12/13

type

enclosure

barrier type auxiliary alarm terminal block(s)

cabinet

heater

assembly

external temperature compensation probe

pad lock for front panel door

DNP3 Level 2 / Modbus communications module

zero-center ground detect meter

forced load sharing interconnection cable

Please find the serial number on the

data nameplate and record it here: