Servicing the at10.1 – Exide Technologies Section 94.20 User Manual
Page 48

SERVICING THE AT10.1
44
3. SERVICING THE AT10.1
3.1. A STEP-BY-STEP TROUBLESHOOTING PROCEDURE
The AT10.1 battery charger is fully tested and calibrated at the factory and 
should work for years with a minimum of attention. If you do encounter 
trouble, there are three steps you should take to find the problem and 
return the charger to service. 
1. Check the front panel meter for an error code. The AT10.1 is able to
diagnose common problems with the battery charger, or with the application 
or installation. If the front panel displays an error code, see Section 3.2, 
Interpreting Front Panel Error Messages, for help in interpreting the code 
and solving the problem. 
2. If the charger does not work properly, but there is no front panel error code,
turn off the front panel circuit breakers (or disconnect ac and dc power 
externally). Then turn the dc and ac power back on. This will return the 
charger to normal operation as long as there is no internal component failure. 
Note: Do this only once. If the charger does not resume 
normal operation, go to the next step. 
3. If the charger still does not work properly, make a list of the symptoms that
you observe, then turn to Using the troubleshooting chart in Section 3.3. The 
troubleshooting chart relates common trouble symptoms to their causes, and 
gives the proper procedures for correcting the problem. 
4. If the symptom doesn't appear on the troubleshooting chart, or if the
recommended repair doesn't work, consult your sales or service 
representative to arrange for on-site or factory service. 