APPENDIX A

70

SPECIFICATIONS

Except as noted, all specifications apply at:

77

° F / 25 °C, nominal ac line voltage & nominal float voltage

Specification Conditions

12 Vdc 24 Vdc 48 Vdc 130 Vdc

Output voltage regulation

Vac +10%, -12%
0 to 100% load
Temp. 32-122

° F / 0-50° C

Freq. 60

± 3 Hz

± 0.25%

(see product literature for specific data)

Transient response

20-100% load change,
with battery connected

Output voltage change

± 4% maximum

Recovery to

± 2.0% in 200 ms

Recovery to

± 0.5% in 500 ms

12 Adc rating, full load (%)

67.00 72.00 78.00 85.00

Efficiency

25 Adc rating, full load (%)

73.00

77.00

85.00

91.00

1% rms (typ)

2% rms

Unfiltered (with battery)

at battery terminals

30 mV rms (max)

100 mV

Filtered (with battery)

at battery terminals

Filtered (without battery)

1% rms (typ)

2% rms

Output ripple voltage
per NEMA PE5-1996

Battery Eliminator Filter
Option (without battery)

30 mV rms

100 mV

Current limit

Adjustable

50-110 % of rated output current

Soft start

0 to 100% load

4 seconds

Float (Vdc)

11.0-14.5 22.0-29.5 44.0-58.0

110-141

Equalize (Vdc)

11.7-15.5 23.4-31.0 46.8-59.0

117-143

High DC Voltage alarm (Vdc)

12-19 24-38 48-76

120-175

Voltage adjustment ranges

Low DC Voltage alarm (Vdc)

7-14.5 15-29.5 30-58 80-141

Voltmeter range (Vdc)

0 - 21

0 - 42

0 - 75

0 - 195

Ammeter range (Adc)

All ratings

0 - 30

Surge withstand capability

Test per
ANSI C37.90.1-1989

No erroneous outputs

Reverse current from
battery

AC input power failure

90 mA maximum

Audible noise

Average for 4 sides,
5ft / 1.5m from charger

Less than 62 dB(A)

Cooling

Natural

convection

Ambient temperature

Operating

32-122

° F / 0-50° C

Elevation

3000ft / 1000m without derating

Relative humidity

0 to 95% non-condensing

Alarm relay contact rating

120 Vac / 125 Vdc

0.5 A resistive