APPENDIX A
70
SPECIFICATIONS
Except as noted, all specifications apply at:
77
° F / 25 °C, nominal ac line voltage & nominal float voltage
Specification Conditions
12 Vdc 24 Vdc 48 Vdc 130 Vdc
Output voltage regulation
Vac +10%, -12%
0 to 100% load
Temp. 32-122
° F / 0-50° C
Freq. 60
± 3 Hz
± 0.25%
(see product literature for specific data)
Transient response
20-100% load change,
with battery connected
Output voltage change
± 4% maximum
Recovery to
± 2.0% in 200 ms
Recovery to
± 0.5% in 500 ms
12 Adc rating, full load (%)
67.00 72.00 78.00 85.00
Efficiency
25 Adc rating, full load (%)
73.00
77.00
85.00
91.00
1% rms (typ)
2% rms
Unfiltered (with battery)
at battery terminals
30 mV rms (max)
100 mV
Filtered (with battery)
at battery terminals
Filtered (without battery)
1% rms (typ)
2% rms
Output ripple voltage
per NEMA PE5-1996
Battery Eliminator Filter
Option (without battery)
30 mV rms
100 mV
Current limit
Adjustable
50-110 % of rated output current
Soft start
0 to 100% load
4 seconds
Float (Vdc)
11.0-14.5 22.0-29.5 44.0-58.0
110-141
Equalize (Vdc)
11.7-15.5 23.4-31.0 46.8-59.0
117-143
High DC Voltage alarm (Vdc)
12-19 24-38 48-76
120-175
Voltage adjustment ranges
Low DC Voltage alarm (Vdc)
7-14.5 15-29.5 30-58 80-141
Voltmeter range (Vdc)
0 - 21
0 - 42
0 - 75
0 - 195
Ammeter range (Adc)
All ratings
0 - 30
Surge withstand capability
Test per
ANSI C37.90.1-1989
No erroneous outputs
Reverse current from
battery
AC input power failure
90 mA maximum
Audible noise
Average for 4 sides,
5ft / 1.5m from charger
Less than 62 dB(A)
Cooling
Natural
convection
Ambient temperature
Operating
32-122
° F / 0-50° C
Elevation
3000ft / 1000m without derating
Relative humidity
0 to 95% non-condensing
Alarm relay contact rating
120 Vac / 125 Vdc
0.5 A resistive