INSTALLING THE AT10.1

CHANGING TRANSFORMER TAPS - GRAPHICS

TYPICAL FOR TRANSFORMER

IN 594 ENCLOSURE

TYPICAL FOR TRANSFORMER

IN 586 ENCLOSURE

H1

H3

H2

H5

H4

H1 H3

H2

H5

H4

JUMPERS (2)

PROCEDURE:

.

1) BE SURE ALL VOLTAGES ARE DE-ENERGIZED AND LOCKED OUT.

2) BE SURE TERMINALS ARE FULLY SEATED (586 ENCL).

3) BE SURE STUD TERMINALS ARE TIGHT (594 ENCL).

4) CHECK YOUR WORK AFTER COMPLETION.

5) FOR ADDITIONAL INFORMATION, SEE WIRING DIAGRAM

IN APPENDIX.

F1-5R2

T1 CONNECTION TABLE

INPUT VAC

JUMPERS

120

H1-H3, H2-H5

208

H2-H4 (2) JUMPERS

240

H2-H3 (2) JUMPERS

480

NONE

TRANSFORMER SCHEMATIC

SECONDARY

H4

H5

H2

H3

H1

X1

X4

Y2

Y1

H5

H1

480 V

PRIMARY

PRIMARY

120/208/240 V

11