Section 3.4, Servicing the at10.1, Troubleshooting chart – Exide Technologies Section 94.20 User Manual
Page 53

SERVICING THE AT10.1
49
3.4. TROUBLESHOOTING CHART
SYMPTOM
PROBABLE
CAUSE
RECOMMENDED ACTION
Front panel 
meter 
displays all 
segments 
"On" or all 
segments 
"Off." AT10.1 
may have no 
output. 
1. An external 
surge has 
interrupted 
operation of the 
microprocessor 
or the display 
controller. 
1A. Soft Reset of control board by pressing S7 reset switch. 
S7 is located inside the AT10.1, on the control board's right 
edge (as viewed from the rear of the front panel). This will 
restart the control board without modifying any settings. 
1B. Hard Reset of control board by pressing and holding the 
"UP" button on the front panel, and simultaneously pressing 
S7 reset switch. This will restart the control board and restore 
all settings to factory default. Reset parameters per Section 
2.3 of this manual. 
1C. Remove all power from AT10.1 to allow control board to 
discharge all voltages. This can be done by opening the AC 
circuit breaker and disconnecting the control board plug(s). 
Keep power removed for approximately 5 minutes to allow 
voltages to discharge. 
AC breaker 
trips 
immediately 
1. Shorted 
rectifier diode 
or SCR 
 
 
2. Defective 
wiring to T1 or 
to the rectifier 
heat sink 
assembly 
3. Defective 
transformer T1 
1. Test by disconnecting wire # 12 from the rectifier assembly. 
Measure resistance between the two top rectifier terminals 
(labeled "AC" on the wiring diagram); it should be at least 
100,000 Ohms (check both polarities). Replace rectifier 
assembly if resistance is low in either direction. 
2. Check spacing of terminals; check wiring for signs of 
insulation damage, burns, etc. Repair as necessary. 
 
 
 
3. Test by disconnecting wires from X1, X4, Y1 and Y2. If ac 
breaker still trips, replace T1. 
AC breaker 
trips after a 
few minutes 
1. Loose 
connection to 
breaker 
2. Wrong ac 
voltage, or T1 
taps miswired 
3. Open SCR
 
 
4. SCR not 
controllable 
1. Check and tighten connections as required. 
 
 
2. Be sure the T1 primary taps are wired correctly for your 
input voltage. See Section 1.6 for details. 
 
3. Use a clamp-on ammeter to measure the current in wire # 
11 or # 12. If it less than 70% of the dc output current, one of 
the SCRs or diodes is defective. Replace the rectifier module. 
4. Disconnect wire # 24 from terminal E3 of the rectifier 
assembly (near the left front of the enclosure). Restart the 
AT10.1. If You are able to measure output current, one of the 
SCRs is defective. Replace the rectifier module. 
DC breaker 
trips 
immediately 
1. Battery 
connected with 
reverse polarity
2. Defective 
rectifier bridge 
(if unfiltered 
charger)
1. Check and correct battery wiring if necessary. 
 
 
2. Test by disconnecting wire # 12 from the rectifier assembly. 
Measure resistance between the two top rectifier terminals 
(labeled "AC" on the wiring diagram); it should be at least 
100,000 Ohms (check both polarities). Replace rectifier 
assembly if resistance is low in either direction. 
