THERMAL ARC 161 STL, 201 TS

INSTALLATION

Installation 3-2

Manual 0-5203

• Electrical Input Requirements
Operate the welding power source from a single-phase 50/60 Hz, AC power supply. The input voltage must match one

of the electrical input voltages shown on the input data label on the unit nameplate. Contact the local electric utility

for information about the type of electrical service available, how proper connections should be made, and inspection

required. The line disconnect switch provides a safe and convenient means to completely remove all electrical power

from the welding power supply whenever necessary to inspect or service the unit.
Do not connect an input (WHITE or BLACK) conductor to the ground terminal.
Do not connect the ground (GREEN) conductor to an input line terminal.
Refer to Figure 3-1:
1. Connect end of ground (GREEN or GREEN/YELLOW) conductor to a suitable ground. Use a grounding method that

complies with all applicable electrical codes.

2. Connect ends of line 1 (BLACK) and line 2 (WHITE) input conductors to a de-energized line disconnect switch.
3. Use Table 3-1 as a guide to select line fuses for the disconnect switch.

Input Voltage

Circuit Breaker or Fuse Size

115V

30A

208-230V

50A

Table 3-1: Fuse Guide

CAUTION

The time-delay fuses or circuit breaker of an individual branch circuit may have nuisance tripping when

welding with this product due to the amperage rating of the time-delay fuses or circuit breaker.