05 input wiring specifications – Tweco A80-A120 CutMaster User Manual
Page 17
CUTMASTER A80, A120
Manual 0-5119
INTRODUCTION
2-3
Power Supply Dimensions & Weight
Ventilation Clearance Requirements
26.3"
0.668 m
63 lb / 28.6 kg
10"
254 mm
13.78"
350 mm
Art # A-08459
6"
150 mm
24"
610 mm
6"
150 mm
6"
150 mm
Art # A-07925_AB
2.05 Input Wiring Specifications
CutMaster A80 Power Supply Input Cable Wiring Requirements
Input voltage
Freq
Power Input
Suggested Sizes
Volts
Hz
kVA
I
1
max
I
1
eff
Fuse (amps)
Flexible Cord
(mm
2
)
Flexible Cord
(AWG)
3 Phase
380
50
18.4
28
25
35
10
8
400
50
18.7
27
24
35
10
8
Line Voltages with Suggested Circuit Protection and Wire Sizes
Based on National Electric Code and Canadian Electric Code
CutMaster A120 Power Supply Input Cable Wiring Requirements
Input voltage
Freq
Power Input
Suggested Sizes
Volts
Hz
kVA
I
1
max
I
1
eff
Fuse (amps)
Flexible Cord
(mm
2
)
Flexible Cord
(AWG)
3 Phase
380
60
23
35
32
35
6
10
400
50
23.6
34
31
35
6
10
Line Voltages with Suggested Circuit Protection and Wire Sizes
Based on National Electric Code and Canadian Electric Code
NOTE
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.
I1max is taken at TDC rated minimum duty cycle.
I1eff is taken at TDC 100% rated duty cycle