Item Field

Range

Access

Description

NONE, ZONE, CTRL

Default = CTRL

ADV

WARM WEATHER SHUT DOWN

SECTION N

Set the outdoor temperature at which warm weather
shutdown occurs. Select whether the thermostat
follows the tN4 System Control’s or the zone’s WWSD
for scheduled events.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 72°F

(22.0°C)

INST

ADV

WWSD OCCUPIED AND WAKE

SECTION

N

Set the Warm Weather Shut Down (WWSD) temperature
during Occupied and Wake events.
Note: This item is only available when WWSD is set
to Zone.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 60°F

(15.5°C)

INST

ADV

WWSD UNOCCUPIED AND SLEEP

SECTION

N

Set the Warm Weather Shut Down temperature during
Unoccupied and Sleep events.
Note: This item is only available when WWSD is set
to Zone.

ON, OFF

Default = ON

INST

ADV

OPTIMUM START / STOP

SECTION

J

Select whether to use Optimum Start / Stop for
heating.
Note: This item is only available when a heating
schedule is selected.

ADJUS

T MENU

Adjust Menu (4 of 4)

After the last item, the control returns to the first item in the menu.