Error messag es (1 of 4) – tekmar 161 Setpoint Control Installation User Manual
Page 30

© 2007
D 161 - 08/07
30 of 36
Error Messag
es (1 of 4)
No
te
:
Err
or Messages ar
e only visible while in t
he A
d
vanced or Installer access le
ve
l.
Error Messag
e
Description
ADJUS
T ERR
OR
The se
tpoint contr
ol f
ailed t
o
r
ead t
he ADJUS
T menu se
ttings fr
om memor
y and has r
eloaded t
he
fact
or
y def
ault se
ttings. Operation st
ops until t
he ADJUS
T menu se
ttings ar
e check
ed.
No
te
: T
o
clear t
he err
or
, t
he access le
ve
l must be se
t t
o
A
d
vanced bef
or
e checking all se
ttings in
the ADJUS
T menu.
SCENE ERR
OR
The se
tpoint contr
ol f
ailed t
o
r
ead t
he SCENE menu se
ttings fr
om memor
y and has r
eloaded t
he
fact
or
y def
ault se
ttings. The se
tpoint contr
ol continues t
o
operat
e while displa
ying t
his err
or
.
No
te
: T
o
clear t
he err
or
, t
he access le
ve
l must be se
t t
o
A
d
vanced bef
or
e checking all se
ttings in
the SCENE menu.
SCHEDULE ERR
OR
The se
tpoint contr
ol f
ailed t
o
r
ead t
he SC
HEDULE menu se
ttings fr
om memor
y and has r
eloaded
the f
act
or
y def
ault se
ttings. The se
tpoint contr
ol continues t
o
operat
e while displa
ying t
his err
or
.
No
te
: T
o
clear t
he err
or
, t
he access le
ve
l must be se
t t
o
A
d
vanced bef
or
e checking all se
ttings in
the SC
HEDULE menu.
MISCELL
ANE
OUS ERR
O
R
The se
tpoint contr
ol f
ailed t
o
r
ead t
he MISCELL
ANE
OUS menu se
ttings fr
om memor
y and has
re
loaded t
he f
act
or
y def
ault se
ttings. The se
tpoint contr
ol continues t
o
oper
at
e while displa
ying
this err
or
.
No
te
: T
o
clear t
he err
or
, t
he access le
ve
l must be se
t t
o
A
d
vanced bef
or
e checking all se
ttings in
the MISCELL
ANE