Troubleshooting – Banner DUO-TOUCH SG Two-Hand Control Safety Modules User Manual

Page 17

background image

Troubleshooting

Condition: Outputs Will Not Energize

Indicator Status

Possible Reason/Solution

Power

ON

Two-Hand Control Input Simulta-
neity Error

Fault

ON

In #1

ON or OFF

- Simultaneity failure (> 500 ms)
with status of input

In #2

ON or OFF

SSI

ON

MUTE

OFF

OUT

OFF

Indicator Status

Possible Reason/Solution

Power

ON

External Device Monitoring (EDM)
error

Fault

ON

In #1

ON

- Feedback open (Y1/Y2)

In #2

ON

SSI

ON

MUTE

OFF

OUT

Flashing

Indicator Status

Possible Reason/Solution

Power

ON

Two-Hand Control Input Error

Fault

ON

-Input invalid (NO/NC within an in-
put did not switch within 100 ms)

In #1

Flashing or
OFF

In #2

Flashing or
OFF

- Both channels within an input are
closed (S12/S11/S13 or S22/S21/
S23)

SSI

ON

MUTE

OFF

- Both channels within an input are
open (S12/S11/S13 or S22/S21/
S23)

OUT

OFF

Condition: Outputs Will Not Energize

Indicator Status

Possible Reason/Solution

Power

ON

Two-Hand Control Input Short Cir-
cuit

Fault

Flashing

In #1

Flashing

- Input #1 is short circuited to Input
#2 (S12/S11/S13 to S22/S21/S23)

In #2

Flashing

SSI

OFF

MUTE

OFF

OUT

OFF

Indicator Status

Possible Reason/Solution

Power

ON

Safety Stop Interface Error

Fault

Flashing

In #1

ON or OFF

- Invalid Input - SSI channels did
not operate concurrently, both
must open and then both must re-
close (X3/X4 and X5/X6)

In #2

ON or OFF

SSI

Flashing

MUTE

OFF

OUT

OFF

Indicator Status

Possible Reason/Solution

Power

ON

Power-Up Error

Fault

Flashing

NOTE: This error is a non-recovera-
ble lockout; the power must be re-
moved, the Inputs must be deactiva-
ted (cleared or opened) and then
power reapplied.

In #1

Flashing or
OFF

In #2

Flashing or
OFF

- Two-Hand Control Inputs are ac-
tive, tied-down, or miswired at pow-
er-up (corresponds to flashing In#1/
In#2 LEDs)

SSI

OFF

MUTE

Flashing or
OFF

- M1/M2 Input(s) closed at power-up
(corresponds to flashing MUTE
LED)

DUO-TOUCH® SG Two-Hand Control Modules

P/N 109782 Rev.B

www.bannerengineering.com - tel: 763-544-3164