Specifications
Supply Voltage and Current
A1-A2: 115V ac (AT-GM-11KM) or 230V ac (AT-
HM-11KM), +/- 15%; 50/60Hz
B1-B2: 24V dc, +/- 15%, 10% max. ripple
Supply Protection Circuitry
Protected against transient voltages and reverse polari-
ty
Power Consumption
Approx. 4 W/7 VA
Output Configuration
Outputs (K1 and K2): two redundant (total of four)
safety relay (forced-guided) contacts
Contact ratings:
Maximum voltage: 250V ac or 250V dc
Maximum current:
N.O. Safety Output: 6A ac or dc (resistive load)
N.C. Auxiliary Output (51/52): 5A ac or dc (resis-
tive load)
Maximum power:
N.O. Safety Output: 1500 VA, 200 watts
N.C. Auxiliary Output (51/52): 1250 VA, 200 watts
Mechanical life: 50,000,000 operations
Electrical life: 150,000 cycles (typically @ 1.5 kVA
switching power)
NOTE: Transient suppression is recommended when
switching inductive loads. Install suppressors across
load. Never install suppressors across output contacts
(see Warning in
on page 10).
Auxiliary Supply Voltage (for solid-state outputs)
24V dc @ 1A (applied between Y30 and Y31)
Auxiliary Solid-State Output Current
500 mA max., short circuit protected, Y32 is a PNP out-
put, Y33 is an NPN output
Output Response Time
35 milliseconds maximum ON to OFF
Input Requirements
Outputs from actuating devices must each be capable
of switching up to 20 mA @ 12V dc
Simultaneity Monitoring Period
≤ 500 milliseconds
Z1/Z2 Courtesy Voltage
24V dc @ 150 mA (for STB button power, separate
from Auxiliary output, unregulated)
External Device Monitoring (EDM)
One pair of terminals (Y1 and Y2) are provided to mon-
itor the state of external devices controlled by the safe-
ty outputs. Each device must be capable of switching
15 to 30V dc at 10-50 mA.
Muting Device Inputs (M1, M2)
The muting devices work as a pair (M1 and M2). The
simultaneity requirement is that they be “closed” within
3 seconds of each other to initiate a mute condition or
allow a mute cycle, assuming all other conditions are
met. Each muting device must be capable of switching
15 to 30V dc at 10-50 mA.
Mute Enable Input (ME)
Mute Enable input must be closed in order to start a
mute cycle. Opening this input after a mute cycle has
begun has no effect. The switching device must be ca-
pable of switching 15 to 30V dc at 10-50 mA.
Safety Stop Interface (SSI)
This input consists of two concurrent channels (SSI-A
and SSI-B) and is always active. Any time either or
both channels open, the Safety Outputs will go OFF.
When using the SSI, the external device must be capa-
ble of switching 15 to 30V dc at 10-50 mA.
Status Indicators
6 green LED indicators and 1 red LED indicator (see
Figure 1. AT-xM-11KM Status Indicators
on page 3 and
on page 16)
Housing
Polycarbonate. Rated NEMA 1 (IEC IP20)
Mounting
Mounts to standard 35 mm DIN rail track. Safety Mod-
ule must be installed inside an enclosure rated NEMA
3 (IEC IP54), or better.
Vibration Resistance
10 to 55Hz @ 0.35 mm displacement per IEC 68-2-6
Operating Conditions
Temperature: 0° to +50°C (+32° to 122°F)
Maximum Relative Humidity: 90% @ +50°C (non-
condensing)
Heat Dissipation Considerations: See
Safety Category
4 per ISO 13849-1; Type IIIC per ISO 13851 (EN574)
Certifications
Approvals in process. Contact factory for more informa-
tion.