Pollution Degree

2

Relay Outputs

Relay Outputs

4 normally open (N.O.) output channels and 1
normally closed (N.C.) auxiliary output
Contacts: AgNi, 5 μm gold-plated

Each normally open output channel is a series connection of contacts
from two forced-guided (mechanically linked) relays, K1-K2. The nor-
mally closed Aux. output channel is a parallel connection of contacts
from two forced-guided relays, K1-K2.

Low Current Rating: The 5 μm gold-plated contacts allow the switching of low current/low voltage. In these low-power applications,
multiple contacts can also be switched in series (e.g., “dry switching”). To preserve the gold plating on the contacts, do not exceed the
following max. values at any time:

Min.

Max.

Voltage

1V ac/dc

60V

Current

5 mA ac/dc

300 mA

Power

5 mW (5 mVA)

7 W (7 VA)

High Current Rating: If higher loads must be switched through one or more of the contacts, the minimum and maximum values of the
contact(s) changes to:

Minimum

Maximum

Voltage

15V ac/dc

N.O. Safety Contacts (13-14, 23-24, 33-34, 43-44):
250V ac / 24V dc, 6A resistive
B300, Q300 (UL508)
N.C. Auxiliary Contact (51-52): 250V ac/ 24V dc, 5A
resistive
B300, Q300 (UL508)

Current

250 mA ac/dc

Power

5 W (5 VA)

Minimum

Maximum — IEC60947-5-1

Voltage

15V ac/dc

N.O. Safety Contacts:
AC-1: 250V ac, 6A; DC-1: 24V dc, 6A
AC-15: 230V ac, 3A; DC-13: 24V dc, 4A
N.C. Auxiliary Contact:
AC-1: 250V ac, 5A; DC-1: 24V dc, 5A
AC-15: 230V ac, 2A; DC-13: 24V dc, 4A

Current

250 mA ac/dc

Power

5 W (5 VA)

Mechanical Life

> 50,000,000 operations

NOTE: Transient suppression is recommended when switch-
ing inductive loads. Install suppressors across load. Never in-
stall suppressors across output contacts (see Warning, Wir-
ing of Arc Suppressors).

Electrical Life

150,000 cycles at 1500 VA
1,000,000 cycles at 450 VA
2,000,000 cycles at 250 VA
5,000,000 cycles at 125 VA

Solid-State Outputs

Two non-safety solid-state dc outputs
Output circuits require application of +12-24V dc ±
15% at terminal Y31; dc common at Y30.
Max. switching current: 100 mA at 12-24V dc

Output Response Time

35 ms max. (25 ms typical)