Rockwell Automation SB3000 Configuration and Programming User Manual
Page 64

3-46
SB3000 Drive Configuration and Programming
Power-Up Self-Calibration Faults
,I DQ\ RI WKH SRZHUXS VHOIFDOLEUDWLRQ IDXOWV RFFXUV UHSODFH WKH $& 3RZHU 7HFKQRORJ\
PRGXOH LQ WKH 6% 5HFWLILHU©V 30, UDFN 1RWH WKDW U
egister 202, bit 11
(FLT_PTM@) will also be set.
Run Time AC Power Technology Module Faults
Diagnostic Fault Code Register
222/1222
The Diagnostic Fault Code register displays an error code to help
diagnose the cause of a problem reported in other registers.
Note that this register is available for monitoring only. It cannot be
referenced in an application task.
Sug. Var. Name:
DIAG_FLT%
Units:
N/A
Range:
N/A
Access:
Read only
Code
Fault
1
D/A high voltage error (+10% out of tolerance)
2
D/A low voltage error (-10% out of tolerance)
3
Torque current loop proportional gain not within calibration limits
4
Flux current loop proportional gain not within calibration limits
5
Flux current loop integrator time constant not within calibrated limits
6
Torque current loop integrator time constant not within calibrated limits
7
Harmonic injection error
8
Harmonic DAC limit error
9
Harmonic DAC low error
10
Harmonic DAC range error
11
Programmable current limit fault
12
VAC integrator error
13
A/D converter interrupt error
14
Pulse Width Modulator frequency error
15
DC bus current not zero at power-up.
16
Phase U current not zero at power-up.
17
Phase W current not zero at power-up.
Code
Fault
Description/Action
20
Power supply monitor tripped
Power supply level on the AC Power
Technology module (ACPTM) out of
tolerance.
Replace the ACPTM, PMI rack, and/or
Power Supply.
21
AC power technology
watchdog time-out
ACPTM watchdog timer has expired.
Replace the ACPTM, PMI rack, and/or
Power Supply.