Rockwell Automation SB3000 Configuration and Programming User Manual
Page 63
![background image](/manuals/581665/63/background.png)
Configuring the UDC Module’s Registers
3-45
Parallel Power Module C Status Register (Continued)
221/1221
GDI Fault C
Bit 7
The GDI Fault C bit is set if a fault is
detected in the power supply of Power
Module C’s Gate Driver Interface module.
Hex Value:
0080H
Sug. Var. Name:
GDIC@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Charge Fault C
Bit 8
The Charge Fault C bit is set if a charge bus
time-out fault occurs in Power Module C
(refer also to register 202/1202, bit 6).
Hex Value:
0100H
Sug. Var. Name:
CHGC@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Over Temperature C
Bit 12
The Over Temperature C bit is set if an over
temperature fault or warning occurs in
Power Module C.
Hex Value:
1000H
Sug. Var. Name:
OTC@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Phase U Current Sharing C
Bit 13
The Phase U Current Sharing C bit is set if a
Power Module C is not carrying its share of
the phase U current.
Hex Value:
2000H
Sug. Var. Name:
U_SHRC@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Phase V Current Sharing C
Bit 14
The Phase V Current Sharing C bit is set if
Power Module C is not carrying its share of
the phase V current.
Hex Value:
4000H
Sug. Var. Name:
V_SHRC@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Phase W Current Sharing C
Bit 15
The Phase W Current Sharing C bit is set if
Power Module C is not carrying its share of
the phase W current.
Hex Value:
8000H
Sug. Var. Name:
W_SHRC@
Access:
Read only
UDC Error Code:
N/A
LED: