SB3000 Drive Configuration and Programming
Parallel Power Module B Status Register (Continued)
220/1220
Phase W-Lower IOC B
Bit 5
The Phase W-Lower B status bit is set if an
IOC or DSAT fault occurs in Power Module
B’s phase W, lower power device.
Hex Value:
0020H
Sug. Var. Name:
W_LOB@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Intelligent Power Module B
Bit 6
The Intelligent Power Module B bit is set to
indicate that a DSAT (shoot-through) fault
has occurred in Power Module B.
Hex Value:
0040H
Sug. Var. Name:
IPUB@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Bits 0 - 5 of this register should be checked to identify the device in which the fault
occurred.
GDI Fault B
Bit 7
The GDI Fault B bit is set if a fault is
detected in the power supply of Power
Module B’s Gate Driver Interface module.
Hex Value:
0080H
Sug. Var. Name:
GDIB@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Charge Fault B
Bit 8
The Charge Fault B bit is set if a charge bus
time-out fault occurs in Power Module B
(refer also to register 202/1202, bit 6).
Hex Value:
0100H
Sug. Var. Name:
CHGB@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Over Temperature B
Bit 12
The Over Temperature B bit is set if an over
temperature fault or warning occurs in
Power Module B.
Hex Value:
1000H
Sug. Var. Name:
OTB@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A