Rockwell Automation SB3000 Configuration and Programming User Manual
Page 41

Configuring the UDC Module’s Registers
3-23
Drive Status Register (Continued)
200/1200
Power Factor Current In Limit
Bit 3
The Power Factor Current in Limit bit is set if
the power factor current is being limited by
the PMI to keep the current minor loop from
saturating.
Hex Value:
0008H
Sug. Var. Name:
IPF_LMT@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Line Synchronized
Bit 7
The Line Synchronized bit is set when the
PMI Processor is synchronized to the AC
line. This bit is valid when the Rectifier has
input power, whether the voltage control
loop is on or not.
Hex Value:
0080H
Sug. Var. Name:
LIN_SYN@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
If this bit is not on when VDC_RUN@ is commanded, an Interlock failure will occur.
See the description of the IC_SYN@ bit (register 205/1205, bit 6).
Fault Detected
Bit 8
The Fault Detected bit is set if any fault is
detected in the Rectifier. This bit is reset by
bit 8 of register 100/1100.
Hex Value:
0100H
Sug. Var. Name:
FLT@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
See the description of the Drive Fault register (202/1202) for more information.
Warning Detected
Bit 9
The Warning Detected bit is set if any
warning is detected in the Rectifier. This bit
is reset by bit 9 of register 100/1100.
Hex Value:
0200H
Sug. Var. Name:
WRN@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
See the description of the Drive Warning register (203/1203) for more information.