SP500 System Planning
3-7
1. Note that the lead lengths listed are valid with Reliance Electric inverter duty motors.
2. N/A indicates that the drive does not have this rating or it is not applicable.
.
1. MTE standard reactors can be used on SP500 drives with carrier frequency settings up to 8 kHz.
2. All reactors listed are UL-recognized (UL-506 File #E53094) and CSA certified (CSA File #LR29753).
Table 3.7 – Motor Lead Lengths
SP500 HP
Rating
Filter Type
Maximum Lead
Length in Feet with
230 VAC Motor
Maximum Lead
Length in Feet with
460 VAC Motor
Maximum Lead
Length in Feet with
575 VAC Motor
Carrier Frequency
Carrier Frequency
Carrier Frequency
4 kHz
6 kHz
8 kHz
4 kHz
6 kHz
8 kHz
4 kHz
6 kHz
8 kHz
1
None
500
500
500
250
250
250
150
150
150
2
500
500
500
350
350
350
250
200
200
3
1000
1000
1000
400
400
400
250
200
200
5
1000
1000
1000
500
500
500
250
200
200
7.5 to 10
N/A
N/A
N/A
500
500
500
250
250
250
15 to 20
N/A
N/A
N/A
500
500
500
N/A
N/A
N/A
1
A 5% MTE
reactor/filter at the
drive.
A reactor/filter is not
required. Above lead
lengths are maximum
distances.
500
500
500
500
500
500
2
500
500
500
500
500
500
3
1000
1000
1000
1000
1000
1000
5
1000
1000
1000
1000
1000
1000
7.5 to 10
N/A
N/A
N/A
1000
1000
1000
1000
1000
1000
15 to 20
N/A
N/A
N/A
1000
1000
1000
N/A
N/A
N/A
Table 3.8 – Reactors
SP500 HP Rating
230 Volt
5% MTE Reactor
480 Volt
5% MTE Reactor
600 Volt
5% MTE Reactor
1
RL-00402
RL-00202
RL-00203
2
RL-00403
RL-00404
3
RL-00403
RL-00404
5
RL-00803
RL-00804
7.5
RL-01203
RL-00803
10
RL-01803
RL-01203
15
RL-02503
20
RL-03503