96

Rockwell Automation Publication ENET-RM002C-EN-P - May 2013

Chapter 5

Predict System Performance

For example, use the worksheet in Appendix A for each of the five EtherNet/IP
modules as follows.

The total pps of 220 is well within the 1756-EN2T/A module’s, firmware
revision 2.003, remaining bandwidth of 9000 pps.

EtherNet/IP Modules 2 and 3 with Consumed Tags

EtherNet/IP modules 2 and 3 interface two consumer controllers to the network.

EtherNet/IP Module ID:

4 - 8

Rack-optimized Connections

1 @ 20 ms

= (2 x connections)/RPI

= (2 x 1)/ 20 ms =

100

Direct Connections

3 @ 50 ms

= (2 x connections)/RPI

= (2 x 3)/ 50 ms =

120

Produced Tag Connections

0

= (1 + connections)/RPI

for each produced tag

=

N/A

Consumed Tags

0

= 2/RPI for each consumed tag

=

N/A

Total Packets Per Second

220

1756-EN2T Module 2

1756-EN2T Module 3