Table 14 - Additional ControlLogix EtherNet/IP Communication Module Specifications

Cat. No.

Series Firmware

Revision

RSLogix 5000
Software Version

RSLinx Software
Version

Packet Rate Capacity (packets/ second)

(2)

Support for
Extended
Environment

(4)

Integrated Motion
on the EtherNet/IP
Network Axes

I/O

HMI/MSG

1756-ENBT

Any

Any

8.02.00 or later

2.30 or later

5000

900

No

N/A

1756-EN2F

A

2.x

15.02.00 or later

2.51 or later

10,000

2000

No

N/A

3.6 or later

18.02.00 or later

(1)

25,000

(3)

Up to 4 axes
supported

(5)

B

Up to 8 axes
supported

(5)

1756-EN2T

A

2.x or earlier

15.02.00 or later

2.51 or later

10,000

2000

No

N/A

3.6 or later

18.02.00 or later

(1)

25,000

(3)

Up to 4 axes
supported

(5)

B

2.x

15.02.00 or later

10,000

N/A

3.6 or later

18.02.00 or later

(1)

25,000

(3)

Up to 4 axes
supported

(5)

C

Up to 8 axes
supported

(5)

1756-EN2TXT

B

2.x

15.02.00 or later

2.51 or later

10,000

2000

Yes

N/A

3.6 or later

18.02.00 or later

(1)

25,000

(3)

Up to 4 axes
supported

(5)

C

Up to 8 axes
supported

(5)

1756-ENT2TR

A

2.x

17.01.02 or later

2.55 or later

10,000

2000

No

N/A

3.6 or later

18.02.00 or later

(1)

2.56 or later

25,000

(3)

Up to 4 axes
supported

(5)

B

Up to 8 axes
supported

(5)

1756-EN2TRXT

A

5.028 or later

20.01.00 or later

2.56 or later

25,000

(3)

2000

Yes

N/A

1756-EN2TSC

A

5.028 or later

20.01.00 or later

2.56 or later

25,000

(3)

930 with encryption
1800 without encryption

No

N/A

1756-EN3TR

A

3.6 or later

18.02.00 or later

(1)

2.56 or later

25,000

(3)

2000

No

Up to 255 axes
supported

(5)

9300-ENA

A

1.12 or later

N/A

N/A

N/A

No

N/A

(1) This version is required to use CIP Sync technology, Integrated Motion on the EtherNet/IP Network, or Exact Match keying.
(2) For more information on Packet Rate Capacity, see

Packets Rate Capacity on page 69

.

(3) The packet rate capacity can change slightly depending on the firmware revision of your EtherNet/IP communication module. For more information, see

Packets Rate Capacity on page 69

.

(4) Module operates in a broad temperature spectrum, -20…70 ºC (-4…158 ºF), and meets ANSI/ISA-S71.04-1985 Class G1, G2 and G3, as well as cULus, Class 1 Div 2, C-Tick, CE, ATEX Zone 2 and SIL 2

requirements for increased protection against salts, corrosives, moisture/condensation, humidity, and fungal growth.

(5) This value assumes the use of a 1756-L7x ControlLogix controller. For a 1756-L6x ControlLogix controller, see ControlLogix Controllers User Manual, publication

1756-UM001

.