Rockwell Automation Ethernet Design Considerations Reference Manual User Manual
Page 68
![background image](/manuals/581480/68/background.png)
68
Rockwell Automation Publication ENET-RM002C-EN-P - May 2013
Chapter 4
EtherNet/IP Protocol
Table 14 - Additional ControlLogix EtherNet/IP Communication Module Specifications
Cat. No.
Series Firmware
Revision
RSLogix 5000
Software Version
RSLinx Software
Version
Packet Rate Capacity (packets/ second)
(2)
Support for
Extended
Environment
(4)
Integrated Motion
on the EtherNet/IP
Network Axes
I/O
HMI/MSG
1756-ENBT
Any
Any
8.02.00 or later
2.30 or later
5000
900
No
N/A
1756-EN2F
A
2.x
15.02.00 or later
2.51 or later
10,000
2000
No
N/A
3.6 or later
18.02.00 or later
(1)
25,000
(3)
Up to 4 axes
supported
(5)
B
Up to 8 axes
supported
(5)
1756-EN2T
A
2.x or earlier
15.02.00 or later
2.51 or later
10,000
2000
No
N/A
3.6 or later
18.02.00 or later
(1)
25,000
(3)
Up to 4 axes
supported
(5)
B
2.x
15.02.00 or later
10,000
N/A
3.6 or later
18.02.00 or later
(1)
25,000
(3)
Up to 4 axes
supported
(5)
C
Up to 8 axes
supported
(5)
1756-EN2TXT
B
2.x
15.02.00 or later
2.51 or later
10,000
2000
Yes
N/A
3.6 or later
18.02.00 or later
(1)
25,000
(3)
Up to 4 axes
supported
(5)
C
Up to 8 axes
supported
(5)
1756-ENT2TR
A
2.x
17.01.02 or later
2.55 or later
10,000
2000
No
N/A
3.6 or later
18.02.00 or later
(1)
2.56 or later
25,000
(3)
Up to 4 axes
supported
(5)
B
Up to 8 axes
supported
(5)
1756-EN2TRXT
A
5.028 or later
20.01.00 or later
2.56 or later
25,000
(3)
2000
Yes
N/A
1756-EN2TSC
A
5.028 or later
20.01.00 or later
2.56 or later
25,000
(3)
930 with encryption
1800 without encryption
No
N/A
1756-EN3TR
A
3.6 or later
18.02.00 or later
(1)
2.56 or later
25,000
(3)
2000
No
Up to 255 axes
supported
(5)
9300-ENA
A
1.12 or later
N/A
N/A
N/A
—
No
N/A
(1) This version is required to use CIP Sync technology, Integrated Motion on the EtherNet/IP Network, or Exact Match keying.
(2) For more information on Packet Rate Capacity, see
Packets Rate Capacity on page 69
(3) The packet rate capacity can change slightly depending on the firmware revision of your EtherNet/IP communication module. For more information, see
Packets Rate Capacity on page 69
(4) Module operates in a broad temperature spectrum, -20…70 ºC (-4…158 ºF), and meets ANSI/ISA-S71.04-1985 Class G1, G2 and G3, as well as cULus, Class 1 Div 2, C-Tick, CE, ATEX Zone 2 and SIL 2
requirements for increased protection against salts, corrosives, moisture/condensation, humidity, and fungal growth.
(5) This value assumes the use of a 1756-L7x ControlLogix controller. For a 1756-L6x ControlLogix controller, see ControlLogix Controllers User Manual, publicat